Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 16 07.07.16
Wiring Diagram M: EcoSystemR Dimming Power Module for 3-wire LutronR Dimming Ballast / drivers
— 1 Distribution Panel / 1 Feed
L2/H2 100-277 V~
E1
E1
+20V
Common
IR
OCC
Daylight
E2
E2
Class 2 Sensors
Capteurs Classe 2
Sensores Clase 2
Class 2 Link
Lien Classe 2
Enlace Clase 2
EcoSystem
®
Multiple Fixture Dimming Control
Contrôle de gradation de multiples luminaires
Control atenuador de múltiples lámparas
PWR
STAT
Indicateur de puissance (PWR)
On: l’unité est alimentée
Off: l’unité n’est pas alimentée
ou est dysfonctionnelle
Indicateur d’activité (STAT)
Plein: Niveau de circuit
Impulsion: Aucune
communication
Power Indicator (PWR)
On: Unit is powered
Off: Unit is not powered
or is malfunctioning
Status Indicator (STAT)
Solid: Circuit Level
Pulse: No communication
Indicador de Alimentación (PWR)
Encendido: unidad tiene corriente
Apagado: unidad no tiene corriente
o no está funcionando correctamente
Indicador de estado (STAT)
Sólido: Nivel del Circuito
Pulsante: No hay comunicación
C5-BMJ-16A
COM
DYLT
P/N 500-10755
®
GRX-TVI
EcoSystemR
Power
Module
2
To additional ballasts / drivers
EARTH / GROUND
CONNECTIONS
Red
1
Black
Switched Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
White
Orange
Distribution
Panel
Neutral
Earth / Ground
Note: Ballast / driver must
provide a 0—10 V- source
only!
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage in
the range of 100—277 V~. Refer to the
Note on the first page of the GRX-TVI
Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot
output to the load. Shown in picture
as the same voltage as L2 / H2.
Neutral
Green
E1
E2
To additional
EcoSystemR
modules,
ballast / drivers
and EcoSystemR
Bus Supply
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
The red wire is not used. Cap off the red wire using a wire connector. Do not wire the red
wire to ground or to any other wiring.
2
The EcoSytem® Power Module and ballasts / drivers must be rated for the specific
Line / Mains voltage utilized.
16