EcoSystem® Five Control Input Digital Dimming Ballasts
369454k 16 05.27.16
Wiring to an IR Receiver and Wallstation
• Wiring summary:
Sensor Wire Ballast Terminal Terminal Color
Red +20 V - Red
Black Common Black
White IR White
Make sure that the supply breaker to the Digital
Ballast is OFF when wiring.
Connect the three conductors to the three Digital
Ballast terminals as shown.
The maximum wire length from the ballast to the
sensor is 50 ft (15 m).
Ballast Class 2 terminals only accept one 22 AWG
(0.34 mm
2
) solid wire.
Notes
Only one wallstation or IR receiver can be wired to a
digital ballast.
If a daylight sensor and wallstation/IR receiver are
connected to one ballast, do not connect the
daylight sensors IR output.
All sensor and wallstation wiring is Class 2. Follow all
applicable national and local codes for proper circuit
separation and protection.
22 AWG (0.34 mm
2
) solid only
G Case Terminals
IR Receiver
J Case Terminals
22 AWG (0.34 mm
2
) solid only
IR Receiver
Wallstation
Wires to Digital Ballast
NEU
DH
SH
LINE
+20V
Common
IR
Occ
Daylight
Class 2 (22 AWG Solid)
Class 2
Bus
E1
E2
+20V
Common
IR
Occ
Daylight
Class 2
(22 AWG Solid)
EcoSystem® Ballast Wiring:
IR Receiver and Wallstation
16