Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Five Control Input Digital Dimming Ballasts
369454k 16 05.27.16
Wiring to an IR Receiver and Wallstation
• Wiring summary:
Sensor Wire Ballast Terminal Terminal Color
Red +20 V - Red
Black Common Black
White IR White
• Make sure that the supply breaker to the Digital
Ballast is OFF when wiring.
• Connect the three conductors to the three Digital
Ballast terminals as shown.
• The maximum wire length from the ballast to the
sensor is 50 ft (15 m).
• Ballast Class 2 terminals only accept one 22 AWG
(0.34 mm
2
) solid wire.
Notes
• Only one wallstation or IR receiver can be wired to a
digital ballast.
• If a daylight sensor and wallstation/IR receiver are
connected to one ballast, do not connect the
daylight sensor’s IR output.
• All sensor and wallstation wiring is Class 2. Follow all
applicable national and local codes for proper circuit
separation and protection.
22 AWG (0.34 mm
2
) solid only
G Case Terminals
IR Receiver
J Case Terminals
22 AWG (0.34 mm
2
) solid only
IR Receiver
Wallstation
Wires to Digital Ballast
NEU
DH
SH
LINE
+20V
Common
IR
Occ
Daylight
Class 2 (22 AWG Solid)
Class 2
Bus
E1
E2
+20V
Common
IR
Occ
Daylight
Class 2
(22 AWG Solid)
EcoSystem® Ballast Wiring:
IR Receiver and Wallstation
16