EcoSystem® Ballast Wiring:
Occupancy Sensor
Wiring to a LutronR Occupancy Sensor (LOS-XX)
• Sensor wiring summary:
Sensor Wire Ballast Terminal Terminal Color
Red +20 V - Red
Black Common Black
Blue Occ Blue
• Make sure that the supply breaker to the Digital
Ballast is OFF when wiring.
• Connect the three conductors to the three ballast
terminals as shown.
• The maximum wire length from the ballast to the
sensor is 50 ft (15 m).
• Ballast Class 2 terminals only accept one 22 AWG
(0.34 mm
2
) solid wire.
Notes
• Occupancy sensors from other manufacturers may be
used with EcoSystem
® ballasts if the sensor meets the
following criteria:
Vin = +20 V - current draw less than 35 mA
• If other manufacturer’s occupant sensors are used
terminal colors and sensor wire colors may not match.
• All sensor and wallstation wiring is Class 2. Follow all
applicable national and local codes for proper circuit
separation and protection.