EcoSystem® Ballast Wiring:
Occupancy Sensor
Wiring to a LutronR Occupancy Sensor (LOS-XX)
Sensor wiring summary:
Sensor Wire Ballast Terminal Terminal Color
Red +20 V - Red
Black Common Black
Blue Occ Blue
Make sure that the supply breaker to the Digital
Ballast is OFF when wiring.
Connect the three conductors to the three ballast
terminals as shown.
The maximum wire length from the ballast to the
sensor is 50 ft (15 m).
Ballast Class 2 terminals only accept one 22 AWG
(0.34 mm
2
) solid wire.
Notes
Occupancy sensors from other manufacturers may be
used with EcoSystem
® ballasts if the sensor meets the
following criteria:
Vin = +20 V - current draw less than 35 mA
If other manufacturer’s occupant sensors are used
terminal colors and sensor wire colors may not match.
All sensor and wallstation wiring is Class 2. Follow all
applicable national and local codes for proper circuit
separation and protection.