Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Five Control Input Digital Dimming Ballasts
369454k 12 05.27.16
To the EcoSystem® digital link & up to
64 total ballasts, drivers, or modules
EcoSystem® Ballast Wiring:
EcoSystem
® Digital Link
EcoSystem® Digital Link Overview
• The EcoSystem
® digital link wiring (E1 and E2)
connects the ballasts together to form a lighting
control system.
• Each EcoSystem
® digital link supports up to 64 digital
ballasts, 64 occupant sensors, 16 daylight sensors,
and 64 wallstations or IR receivers.
• E1 and E2 (EcoSystem
® digital link wires) are polarity
insensitive and can be wired in any topology.
• An EcoSystem
® Energi Savr NodeTM device, GRAFIK
Eye
® QS with EcoSystem® connection, or Quantum®
system provides power for the EcoSystem
® digital link
and supports system programming.
• All EcoSystem
® digital link programming is completed
by using the EcoSystem
® Programmer,
GRAFIK Eye
® QS with EcoSystem® connection, or
Quantum
® system.
EcoSystem
® Digital Link Wiring
• Driver EcoSystem
® digital link terminals only accept
one solid wire per terminal from 18 AWG to 16 AWG
(0.75 mm
2
to 1.5 mm
2
).
• Make sure that the supply breaker to the ballast and
EcoSystem
® digital link supply is OFF when wiring.
• Connect the two conductors to the two driver
terminals E1 and E2.
• Using two different colors for E1 and E2 will reduce
confusion when wiring several ballasts together.
• The EcoSystem
® digital link may be wired Class 1 or
Class 2. Consult applicable electrical codes for proper
wiring practices.
Notes
• The EcoSystem
® digital link supply does not have
to be located at the end of the digital link.
• E1 and E2 wires are not polarity sensitive.
• EcoSystem
® digital link length is limited by the wire
gauge used for E1 and E2 as follows:
Wire Gauge Digital Link Length
(max)
12AWG 2200ft
14AWG 1400ft
16AWG 900ft
18AWG 550ft
Wire Size Digital Link Length
(max)
4.0mm
2
828m
2.5mm
2
517m
1.5mm
2
310m
1.0mm
2
207m
0.75mm
2
155m
Ballast Terminals
Ballast Terminals
NEU
DH
HOT
LINE
Class 2
Bus
E1
E2
NEU
DH
HOT
LINE
Class 2
Bus
E1
E2