Cut Sheet

SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Diva® 0–10 V Control Wallbox Controls
369147b 3 09.08.14
Specifications (continued)
DVTV- Models
Power
Operating Voltage
24 V- 100 mA
Output Ratings
Power Pack required for load switching. Power Pack is
rated for 16 A
30 mA maximum output, sink ONLY.
0–10 V Control Link
010 V control is Class 2
Controls up to 15 ballasts or drivers (IEC 60929 Annex
E.2 requires the ballast / driver to limit the current draw
to 2.0 mA maximum)
Performance
For 120-277 V~ installations switching more
than 8 A, use DVTV- with Lutron
® Power Pack
(model PP-DV; see Lutron
® P/N 369544).
For 347 V~ installations, use DVTV- with Lutron
®
Power Pack (model PP-347H; see Lutron
®
P/N 369544).
Works with all ballasts and drivers that provide a
current source compliant to IEC 60629 Annex E.2.
Adjustable high-end and low-end trim for optimal
dimming performance.
Power failure memory: should power be interrupted,
the 010 V- signal will return to its previously set level
prior to the interruption when power is restored.
Captive linear slider.
Precise color matching.
Environment
For Indoor Use Only.
Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0% to 90% humidity.
Application Requirements
No derating required if ganged.
Night light not available.
• Always consult local wiring codes.
Warranty
1 Year Limited Warranty. For additional Warranty
information, please visit
www.lutron.com/TechnicalDocumentLibrary/
369-119_Wallbox_Warranty.pdf
3