Cut Sheet
11 | Lutron
* Need to drill new mounting holes in the fixture
Notes
1. When replacing the F-can or B-can with a K-can, it is important to know whether the ballast is mounted by the
studs or the flanges.
2. K-can ballast is wider than the F-can. This may be an issue in narrow fixtures.
3. K-can connector locations don’t exactly match the B-can. They may not line up with fixture mounting plates
in someinstallations.
K-can Replacement Scenarios for T4 CFL Lamps
Replacement Hardware
Existing installation Sample Model Ballast Can Adapter Plate
F-can with studs FDB-CF18-120-2-B K-can with studs CFL-JBA-FAB
F-can without studs FDB-T418-120-2-E K-can without studs N/A*
B-can with studs FDB-T418-120-2-S K-can with studs N/A
B-can without studs FDB-T418-120-2 K-can without studs CFL-BEA-BK
A-can with studs FDB-T418-120-2-S K-Can with studs N/A
A-can without studs FDB-T418-120-2 K-can without studs N/A
ADAPTER PLATES