Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 6 02.02.11
EcoSystem Class 2 Sensor Cable Specifications (continued)
C-CBL-522S-WH-1
General Description
5 conductor EcoSystem sensor cable for non-plenum applications
22AWG(0.34mm
2
)solidbarecopper,PVCinsulatedconductors
Overallaluminum-polymerfoilshield,plus24AWG(0.25mm
2
) copper drain wire
White0.047in(1.2mm)thickPVCjacket—sheathed,UVStabilized
Allexternalmarkingsuseindentedprint
Electrical
Maxoperatingvoltage 300VRMS CL3
600VRMS AWM20811
Maxcontinuouscurrentperconductor 4A at77°F(25°C)
NominalconductorDCresistance 16.5Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -4°Fto221°F(-20°Cto105°C)
Nominal Diameter 0.297 in (7.54 mm)
MaxPullTension 36.0lb(16.33kg)
Min Bend Radius 3 in (76.2 mm)
InsulationMaterial PVC
JacketMaterial PVC
Listings
ULTypeCL3andCM
ULrecognizedAWMStyle20811
UL444, UL13 and UL758
CSA-C22.2No.214
ROHS Compliant
Colors
Jacket - White (WH)
Conductor Color Ballast Terminal
Red +20V
Black Common
White IR
Blue Occupancy
Yellow Daylight
Jacket Markings
LUTRONC-CBL-522S-WH-1PELV/SELV(ULFile#)22AWG5CSHIELDED(UL)CL3
orCMc(UL)us75°CORяUAWM20811105°C600VRoHSCOMPLIANT
6