Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 5 02.02.11
EcoSystem Class 2 Sensor Cable Specifications
C-PCBL-522S-CL-1
General Description
5 conductor EcoSystem sensor cable for plenum spaces
22AWG(0.34mm
2
)solidbarecopper,FEPinsulatedconductors
Overallaluminum-polymerfoilshield,plus24AWG(0.25mm
2
) copper drain wire
Clear0.012in(0.3mm)thickFEPjacket—sheathed
Allexternalmarkingsusewhiteink
Electrical
Maxoperatingvoltage 300VRMS CL3P
Maxcontinuouscurrentperconductor 4A at77°F(25°C)
NominalconductorDCresistance 16.5Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -94°Fto392°F(-70°Cto200°C)
Nominal Diameter 0.140 in (3.56 mm)
MaxPullTension 36.0lb(16.33kg)
Min Bend Radius 1.50 in (38.1 mm)
InsulationMaterial FEP
JacketMaterial FEP
Listings
ULlistedasTypeCL3PorCMPc(UL)us,FT-6
NFPA262
UL444 and UL13
CSA-C22.2No.214
RoHS Compliant
Colors
Jacket—Clear(CL)
Conductor Color Ballast Terminal
Red +20V
Black Common
White IR
Blue Occupancy
Yellow Daylight
Jacket Markings
LUTRONC-PCBL-522S-CL-1(ULFile#)22AWG5CSHIELDED(UL)CL3P
orCMPc(UL)usFT-6200°CRoHSCOMPLIANT