Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 4 02.02.11
EcoSystem Bus Cable Specifications (continued)
C-CBL-216-WH-C1
General Description
For running EcoSystem link with other line-voltage wires (Class 1) in non-plenum applications
16AWG(1.5mm
2
)solidbarecopper,PVC/Nyloninsulatedconductors
2 single conductors cabled
White0.045in(1.1mm)thickPVCjacket—sheathed,UVstabilized
Allexternalmarkingsuseblackink
Electrical
Maxoperatingvoltage 600VRMS TC
600VRMS ULSTANDARD62,TYPETFN
Maxcontinuouscurrentperconductor 20A at77°F(25°C)
NominalconductorDCresistance 4Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -4°Fto194°F(-20°Cto90°C)
Nominal Diameter 0.299 in (7.59 mm)
MaxPullTension 41lb(18.6kg)
Min Bend Radius 1.75 in (44.5 mm)
InsulationMaterial PVCandNylon
JacketMaterial PVC
Listings
ULTypeTCPerULStandard1277fortraycables
CSAListedCICC22.2No.239-09
ULApprovedforSunlightResistance
IndividualConductorsareratedTFN
CablemeetsIEEE383&UL158170,000BTU/HRFlameTestRequirements
CablemeetsICEAS-95-658,whereapplicable
FT-4FlameRating
RoHS Compliant
Colors
Jacket—White(WH)
Conductor Color Ballast Terminal
Purple(PL) E1
Purple+whitestripe(PL/WH) E2
Jacket Markings
C-CBL-216-WH-C1LUTRON(ULFile#)2/16AWG2CTFN(UL)TYPEC600V90°CDRYPVCJACK-
ETSUNRES
orCSALL226471CIC(TC)FT-4RoHSCOMPLIANT
4