Cut Sheet
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 3 02.02.11
EcoSystem Bus Cable Specifications (continued)
C-CBL-216-GR-1
General Description
For running EcoSystem link with other Class 2 wires in non-plenum applications
16AWG(1.5mm
2
)solidbarecopper,PVCinsulatedconductors
2 single conductors cabled
Gray0.03in(0.76mm)thickPVCjacket—sheathed,UVstabilized
Allexternalmarkingsuseblackink
Electrical
Maxoperatingvoltage 300VRMS CL3R/CMG
600VRMS AWMStyle20811
Maxcontinuouscurrentperconductor 13A at77°F(25°C)
NominalconductorDCresistance 4Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -4°Fto221°F(-20°Cto105°C)
Nominal Diameter 0.300 in (7.62 mm)
MaxPullTension 62.5lb(28.35kg)
Min Bend Radius 1.75 in (44.5 mm)
InsulationMaterial PVC
JacketMaterial PVC
Listings
ULTypeCL3R
CMG (C)UL
FT-4FlameRating
AWMStyle20811
UL1666VerticalShaft
RoHS Compliant
Colors
Jacket—Gray(GR)
Conductor Color Ballast Terminal
Purple(PL) E1
Purple+whitestripe(PL/WH) E2
Jacket Markings
C-CBL-216-GR-1LUTRON2/16AWGCL3R90°C(UL)E171202
or CMG c(UL)
orAWMSTYLE20811105°C600VDATECODEFT-4RoHSCOMPLIANT
3