Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem® Cable Low Voltage Cables
369-385 Rev B 2 02.02.11
EcoSystem Bus Cable Specifications
C-PCBL-216-CL-1
General Description
TwoconductorEcoSystem Bus Cable for Plenum Spaces
16AWG(1.5mm
2
)solidbarecopper,FEPinsulatedconductors
2 single conductors cabled
Clear0.017in(0.43mm)thickFEPjacket—sheathed
Allexternalmarkingsusewhiteink
Electrical
Maxoperatingvoltage 300VRMS CL3P
Maxcontinuouscurrentperconductor 10A at77°F(25°C)
NominalconductorDCresistance 4Ohm/1000ft(304.8m) at68°F(20°C)
Physical
TempRating -94°Fto392°F(-70°Cto200°C)
Nominal Diameter 0.173 in (4.39 mm)
MaxPullTension 45lb(20.41kg)
Min Bend Radius 1.75 in (44.5 mm)
InsulationMaterial FEP
JacketMaterial FEP
Listings
ULlistedasTypeCL3PorCMPc(UL)us,FT-6
NFPA262
UL444 and UL13
CSA-C22.2No.214
RoHS Compliant
Colors
Jacket—Clear(CL)
Conductor Color Ballast Terminal
Purple(PL) E1
Purple+whitestripe(PL/WH) E2
Jacket Markings
LUTRONC-PCBL-216-CL-12/16AWG(ULFile#)(UL)CL3P
orCMPc(UL)us200°CFT-6RoHSCOMPLIANT
2