Specification Sheet
177
  www.lutron.com  |  1.800.523.9466  |
Appendix | Lighting load interfaces
 †
UL listed for FULL wattage indicated (derate capacity only if ganged with other devices).
Ceana
® 
pg. 120
Ariadni® 
pg. 124
Glyder® 
pg. 130
Rotary 
pg. 134
Dimmer capabilities and 
interface requirements
M
   Multi-location—true dimming from each location
E
  eco-model available
  Compatible dimmer (no interface)
WBX
TVI
3F
PA
 Requires interface, see notes below
WBX
WBX
WBX
WBX
WBX
WBX
WBX
WBX
WBX
WBX
WBX
   W B X :  Wallbox Phase Adaptive Power Module 
(PHPM-WBX-DV-WH)
   3 F :  Fluorescent Power Module 
(PHPM-3F-DV-WH)
   T V I :  0-10 V Interface 
(GRX-TVI)
   P A :  Phase Adaptive Power Module 
(PHPM-PA-DV-WH)
See pgs. 178–179 for specific compatible dimmer models and switching interface solutions. 
3F
3F
3F
PA
TVI
Dimmers  capacity
†
  Incandescent/halogen 120 V   600 W
E E
1000 W
1500 W
2000 W
  Magnetic low-voltage 120 V  600 VA (450 W)
1000 VA (800 W)
1500 VA (1200 W)
2000 VA (1600 W)
  Magnetic low-voltage 277 V  600 VA (450 W)
1000 VA (800 W)
  Electronic low-voltage 120 V  300 W
4 5 0  W
6 0 0  W
  Electronic low-voltage 277 V  16 A
  Neon/cold cathode
  3-wire ballasts and Hi-lume
® LED driver 120 V  6  A
  Hi-lume, Hi-lume Compact SE,  8 A
  Eco-10
® and EcoSystem® ballasts  16 A
  3-wire ballasts and Hi-lume LED driver 277 V  6  A
  Hi-lume, Hi-lume Compact SE,  8 A
  Eco-10 and EcoSystem ballasts
  16 A
  Tu-Wire
® ballasts 120 V 5 A
  0-10 VDC (ballasts or LED Drivers) 120/277 V  16 A