Installation Guide

Vive Installation
347 V~ Dimming Module with 0 –10 V- Control
347 V~ Emergency Dimming Module with 0 –10 V- Control
Test
Link
Cal.
+
For each system, ensure that you have:
One Dimming Module At least one Wireless Transmitter At least one 0 –10 V- Fluorescent Ballast or LED Driver
Required Components
Radio Powr Savr Occupancy / Vacancy Sensor
(10 maximum)
Radio Powr Savr Daylight Sensor
(1 maximum)
Pico Remote Control
(10 maximum)
60 mA maximum for the control lines. Switches up to 5 A total.
Note: All drivers and ballasts used with Vive wireless controls must comply with the
limits pursuant to CAN ICES-005 and the FCC rules.
Dimming Module (1 maximum)
50019280a
lutron.com
RMJS-5T-347
347 V~ 60 Hz 5 A
0-10 V
Raise
Toggle
Lower
Indicator LED
Consult third-party 0 –10 V- fixtures installation guide for fixture-specific wiring.
+
Occupancy Sensors
Daylight Sensor
Wireless Controls
Occupied: All lights 100%.
Unoccupied: All lights off.
Test
Link
Cal.
All lights dim in response to daylight.
On All lights 100%
Favorite All lights 50%
Off All lights off
Default Functionality
2
A
Dimming Module must be installed in a metal 101.6 mm x
101.6 mm (4 in x 4 in) junction box (minimum depth
54 mm (2.125 in) with mounting screws (provided). Please consult
local and national electric codes for proper installation. Lutron can
provide a barrier, if required, to provide separation in the junction
box between Class 1 and Class 2 wires. Note: if module cannot
be fully seated into the junction box, try rotating the module 90,
180, or 270 degrees. Or move conduit hardware to a different
knockout hole. If neither option works, an extension ring may
be required.
B
Connect bare copper wire from junction box to green
ground screw.
C
Once installed, energize the Dimming Module.
D
Use the Toggle button “ u to toggle between high-end and OFF
to verify ballasts or LED drivers wiring.
E
Use the Raise
and Lower
Δ
” buttons to verify control wiring.
English
All Wireless Transmitters
must be installed within
9 m (30 ft) of the
Dimming Module.
0 –10 V- Control: 10 V- 60 mA (current sink only)
Compatible with ANSI E1.3 2001 (R2006), IEC 60929 Annex E
347 V~ 60 Hz 5 A
RMJS-5T-347
RMJS-5T-347-EM
50019280a
lutron.com
RMJS-5T-347
347 V~ 60 Hz 5 A
0-10 V
Radio Powr Savr
Occupancy
Sensor
Pico
Remote
Control
Dimming
Module
9 m
(30 ft) max
12 m (40 ft)
10 m (33 ft)
Dimming Module
Install in center of room to
maximize RF coverage.
A
Connect mains wiring (switched hot, neutral) to each fixture.
B
Connect 0 –10 V- control (+ and – ) to each fixture.
1
+
NEU
HOT
Class 2
MAINS
Fixture Earth
Green / Yellow
To additional 0 –10 V- fixtures
Neutral
Switched Line/Hot
Violet
Pink
+
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit
breaker before installing the unit.
Sample
ballast shown
50019280a
lutron.com
RMJS-5T-347
347 V~ 60 Hz 5 A
0-10 V
Switched Line / Hot (Red)
– (Pink)
Line / Hot (Black)
To Fixtures
0 –10 V- to Fixtures
(cap wires for non-dim
applications)
Neutral (White)
+ (Violet)
Neutral
Junction Box
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and national
electrical codes.
Note: Use copper conductors only.
Check to see that the device type and rating is suitable for the application.
DO NOT install if product has any visible damage.
If moisture or condensation is evident, allow the product to dry completely before installation.
Operate between 0 °C and 40 °C (32 °F and 104 °F) ambient.
0% to 90% humidity, non-condensing.
For indoor use only.
For application note, see http://www.lutron.com/TechnicalDocumentLibrary/048753.pdf
For spec submittal, see http://www.lutron.com/TechnicalDocumentLibrary/3691140.pdf
May also be used with electronic non-dim (switching) loads. For more
information, see http://www.lutron.com/TechnicalDocumentLibrary/048753.pdf
Class 2 / Class 1 wiring: Install in accordance with all national and local electrical codes.
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Start Here
Programming with a Vive Hub
3
Mount, Wire, and Install 0 –10 V- Devices
and Lighting Fixtures
Consult third-party device installation guide
Install Dimming Module
Suggested Installation Location: Center of room to
ensure proper RF coverage of area.
For optimal RF performance: Module must not be fully
enclosed in metal. No metal should exist anywhere
within 200 mm (8 in) in front of the front plate of the
module. Mount a minimum of 0.6 m (2 ft) away from
the controlled fixture. Ensure the junction box is well
grounded (preferably via a metal conduit between the
controlled fixture and the module junction box).
Note: For further information on set up,
programming, and troubleshooting with a
Vive system, please refer to the installation
instructions included with the Vive hub or visit
www.lutron.com/vive
Note: For programming the Dimming Module
without a Vive hub see reverse side.
Customer Assistance www.lutron.com/support
Troubleshooting www.lutron.com/support
Ballasts or LED drivers cannot be controlled locally from Dimming Module with 0 –10 V-.
Ensure that the breaker(s) to the Dimming Module are energized.
Ensure that the Dimming Module switched hot lead is wired to the lighting fixture(s).
Ensure that the Dimming Module control lines are wired to the lighting fixture(s).
Ensure the driver is a current source for the 0-10 V- link.
Dimming Module may be in emergency mode.
Reset to factory defaults.
Lights do not dim as expected.
Ensure that 0 –10 V- control lines are wired properly.
Ensure that fixture does not require an inverted signal (10 0 V- control).
Ensure the driver is a current source for the 0-10 V- link.
Dimming Module may be in emergency mode.
Lights do not respond to Wireless Transmitter(s) (Pico remotes and RPS sensors).
Ensure that the breaker(s) to the Dimming Module and any connected ballasts or LED drivers are energized.
Ensure that Wireless Transmitters are associated to the Dimming Module.
Reset to factory defaults.
Lights are unstable at low-end or flash/flicker at turn-on or turn-off. Adjust low-end trim.
Wireless Transmitter(s) cannot be associated to Dimming Module with 0 –10 V-.
The maximum number of Wireless Transmitters have been associated to the Dimming Module. To remove a previously set up Wireless Transmitter, tap a Wireless
Transmitter button three times; on the third tap hold for three seconds and then tap three more times.
041765
Rev. A
07/2020
Part of the Vive Family
NOTE: Output must NOT be used to control receptacles. Output must be directly
connected to the load. Output breakers or switches must not be used.
The Vive hub can be set-up easily with any
Wi-Fi enabled iOS® or Android® compatible
device.
A
Download the Lutron Vive app.
B
Open the app and follow the instructions.
vive.lutron.com
X
Wire Connector Information
(1-3) 4.0 mm
2
(10 AWG)
(1-3) 2.5 mm
2
(12 AWG)
(1-3) 1.5 mm
2
(14 AWG)
(1-2) 4.0 mm
2
& (1) 2.5 mm
2
(10 & 12 AWG)
(1-2) 4.0 mm
2
& (1) 1.5 mm
2
(10 & 14 AWG)
(1-2) 2.5 mm
2
& (1) 1.5 mm
2
(12 & 14 AWG)
(1-2) 4.0 mm
2
& (1) 1.0 mm
2
(10 & 16 AWG)
(1-2) 2.5 mm
2
& (1) 1.0 mm
2
(12 & 16 AWG)
(1-2) 1.5 mm
2
& (1) 1.0 mm
2
(14 & 16 AWG)
(1-2) 4.0 mm
2
& (1) 0.75 mm
2
(10 & 18 AWG)
(1-2) 2.5 mm
2
& (1) 0.75 mm
2
(12 & 18 AWG)
(1-2) 1.5 mm
2
& (1) 0.75 mm
2
(14 & 18 AWG)
(1-3) 2.5 mm
2
(12 AWG)
(2-3) 1.5 mm
2
(14 AWG)
(1-2) 2.5 mm
2
& (1) 1.5 mm
2
(12 & 14 AWG)
(1-2) 2.5 mm
2
& (1) 1.0 mm
2
(12 & 16 AWG)
(1-2) 1.5 mm
2
& (1) 1.0 mm
2
(14 & 16 AWG)
(1-2) 2.5 mm
2
& (1) 0.75 mm
2
(12 & 18 AWG)
(1-2) 1.5 mm
2
& (1) 0.75 mm
2
(14 & 18 AWG)
Red
Yellow
1/2 in (13 mm):
10, 12, & 14 AWG
(4.0, 2.5, &
1.5 mm
2
)
5/8 in (16 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 10 AWG (4.0 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(1-3) 14 AWG (1.5 mm
2
)
(1-2) 10 AWG & (1) 12 AWG (4.0 & 2.5 mm
2
)
(1-2) 10 AWG & (1) 14 AWG (4.0 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 10 AWG & (1) 16 AWG (4.0 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 10 AWG & (1) 18 AWG (4.0 & 0.75 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
3/8 in (10 mm):
12 & 14 AWG
(2.5 & 1.5 mm
2
)
7/16 in (11 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(2-3) 14 AWG (1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
Red
Yellow
1/2 in (13 mm):
10, 12, & 14 AWG
(4.0, 2.5, &
1.5 mm
2
)
5/8 in (16 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 10 AWG (4.0 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(1-3) 14 AWG (1.5 mm
2
)
(1-2) 10 AWG & (1) 12 AWG (4.0 & 2.5 mm
2
)
(1-2) 10 AWG & (1) 14 AWG (4.0 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 10 AWG & (1) 16 AWG (4.0 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 10 AWG & (1) 18 AWG (4.0 & 0.75 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
3/8 in (10 mm):
12 & 14 AWG
(2.5 & 1.5 mm
2
)
7/16 in (11 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(2-3) 14 AWG (1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
13 mm (1/2 in):
4.0, 2.5, & 1.5 mm
2
(10, 12, & 14 AWG)
16 mm (5/8 in):
1.0 & 0.75 mm
2
(16 & 18 AWG)
Red
Yellow 10 mm (3/8 in):
2.5 & 1.5 mm
2
(12 & 14 AWG)
11 mm (7/16 in):
1.0 & 0.75 mm
2
(16 & 18 AWG)
200 mm
(8 in)
200 mm
(8 in)
200 mm
(8 in)
200 mm
(8 in)
200 mm
(8 in)
Keep metal
at least
200 mm
(8 in) away
200 mm
(8 in))
200 mm
(8 in)
Note: RMJS-5T-347-EM requires the use of an automatic transfer
switch to change from normal to emergency power. Refer to 048628
for wiring diagrams on www.lutron.com
If installing an emergency Dimming Module and the wiring needs
to be verified, follow “Reset Factory Defaults” procedure to exit
emergency mode.
Please note that any programming will be lost and will have to be
reprogrammed. Only perform this step during initial installation and
wiring verification.
Note: For periodic testing and maintanance of emergency systems,
use the toggle button to ensure proper operation. Make sure buttons
remain accessible.
Note: Momentary power outages can envoke emergency mode on
the dimming module. SeeTroubleshooting section for details.
Note: Violet and pink wires not used for non-dim applications
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
Do not use outdoors.
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may
cause an unsafe condition.
Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS