Installation Guide
041588
Rev. A
04/2020
Vive Installation
347 V~ Dimming Module with 0 –10 V- Control
347 V~ Emergency Dimming Module with 0 –10 V- Control
Test
Link
Cal.
+
For each system, ensure that you have:
One Dimming Module At least one Wireless Transmitter At least one 0 –10 V- Fluorescent Ballast or LED Driver
Required Components
Radio Powr Savr Occupancy / Vacancy Sensor
(10 maximum)
Radio Powr Savr Daylight Sensor
(1 maximum)
Pico Remote Control
(10 maximum)
60 mA maximum for the control lines. Switches up to 5 A total.
Note: All drivers and ballasts used with Vive wireless controls must comply with the
limits for a Class A device, pursuant to Part 15 of the FCC rules.
Dimming Module (1 maximum)
50019280a
lutron.com
RMJS-5T-347
347 V~ 60 Hz 5 A
0-10 V
Raise
Toggle
Lower
Load Status LED
Consult third-party 0 –10 V- fixtures installation guide for fixture-specific wiring.
+
Occupancy Sensors
Daylight Sensor
Wireless Controls
Occupied: All lights 100%.
Unoccupied: All lights off.
Test
Link
Cal.
All lights dim in response to daylight.
On All lights 100%
Favorite All lights 50%
Off All lights off
Default Functionality
2
A
Dimming Module must be installed in a metal 4 in x 4 in
junction box (minimum depth 2 1/8 in) with mounting
screws (provided). Please consult local and national electric
codes for proper installation. Lutron can provide a barrier, if
required, to provide separation in the junction box between
Class 1 and Class 2 wires. Note: if module cannot be
fully seated into the junction box, try rotating the module
90, 180, or 270 degrees. Or move conduit hardware
to a different knockout hole. If neither option works, an
extension ring may be required.
B
Connect bare copper wire from junction box to green
ground screw.
C
Once installed, energize the Dimming Module.
D
Use the Toggle button “ u” to toggle between high-end
and OFF to verify ballasts or LED drivers wiring.
E
Use the Raise “
▲
” and Lower “
Δ
” buttons to verify control
wiring.
English
All Wireless Transmitters must be installed within 30 ft (9 m)
of the Dimming Module.
0 –10 V- Control: 10 V- 60 mA (current sink only)
Compatible with ANSI E1.3 2001 (R2006), IEC 60929 Annex E
347 V~ 60 Hz 5 A
RMJS-5T-347
RMJS-5T-347-EM
50019280a
lutron.com
RMJS-5T-347
347 V~ 60 Hz 5 A
0-10 V
Radio Powr Savr
Occupancy
Sensor
Pico
Remote
Control
Dimming
Module
30 ft
(9 m) max
40 ft (12 m)
33 ft (10 m)
Dimming Module
Install in center of room to
maximize RF coverage.
A
Connect mains wiring (switched hot, neutral) to each fixture.
B
Connect 0 –10 V control (+ and – ) to each fixture.
1
+
–
NEU
HOT
Class 2
MAINS
Fixture Earth
Green/Yellow
To additional 0 –10 V- fixtures
Neutral
Switched Line/Hot
Violet
Pink
+
–
WARNING! Shock Hazard. May result in serious injury or death. Turn off power at circuit
breaker before installing the unit.
Sample
ballast shown
50019280a
lutron.com
RMJS-5T-347
347 V~ 60 Hz 5 A
0-10 V
Switched Line/Hot (Red)
– (Pink)
Line/Hot
(Black)
To Fixtures
0 –10 V- to Fixtures
Neutral (White)
+ (Violet)
Neutral
Junction Box
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes.
• Note: Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 0 °C and 40 °C (32 °F and 104 °F) ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
• For more information and installation tips, see
http://www.lutron.com/TechnicalDocumentLibrary/048753.pdf
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Start Here
Programming with a Vive Hub
3
Mount, Wire, and Install 0 –10 V- Devices
and Lighting Fixtures
Consult third-party device installation guide
Install Dimming Module
Suggested Installation Location: Center of room to
ensure proper RF coverage of area.
Note: For further information
on set up, programming, and
troubleshooting with a Vive system,
please refer to the installation
instructions included with the Vive
hub or visit www.lutron.com/vive
Note: For programming the
Dimming Module without a Vive hub
see reverse side.
Customer Assistance www.lutron.com/support
Troubleshooting www.lutron.com/support
Ballasts or LED drivers cannot be controlled locally from Dimming Module
with 0 –10 V-.
• Ensure that the breaker(s) to the Dimming Module are energized.
• Ensure that the Dimming Module switched hot lead is wired to the lighting fixture(s).
• Ensure that the Dimming Module control lines are wired to the lighting fixture(s).
• Ensure the driver is a current source for the 0-10 V- link.
• Dimming Module may be in emergency mode.
Reset to factory defaults.
Lights do not dim as expected.
• Ensure that 0 –10 V- control lines are wired properly.
• Ensure that fixture does not require an inverted signal (10 – 0 V- control).
• Ensure the driver is a current source for the 0-10 V- link.
• Dimming Module may be in emergency mode.
Lights do not respond to Wireless Transmitter(s)
(Pico remotes and RPS sensors).
• Ensure that the breaker(s) to the Dimming Module and any connected ballasts or LED drivers are energized.
• Ensure that Wireless Transmitters are associated to the Dimming Module.
Reset to factory defaults.
Lights are unstable at low-end or flash/flicker at turn-on or turn-off. • Adjust low-end trim.
Wireless Transmitter(s) cannot be associated to Dimming Module with
0 –10 V-.
• The maximum number of Wireless Transmitters have been associated to the Dimming Module. To remove a previously set up Wireless Transmitter, tap a Wireless Transmitter button three
times; on the third tap hold for three seconds and then tap three more times.
041737
Rev. A
04/2020
Part of the Vive Family
NOTE: Output must NOT be used to control receptacles. Output must be directly
connected to the load. Output breakers or switches must not be used.
The Vive hub can be set-up easily with
any Wi-Fi enabled iOS® or Android®
compatible device.
a. Download the Lutron Vive app.
b. Open the app and follow the instructions.
vive.lutron.com
X
Red
Yellow
1/2 in (13 mm):
10, 12, & 14 AWG
(4.0, 2.5, &
1.5 mm
2
)
5/8 in (16 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 10 AWG (4.0 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(1-3) 14 AWG (1.5 mm
2
)
(1-2) 10 AWG & (1) 12 AWG (4.0 & 2.5 mm
2
)
(1-2) 10 AWG & (1) 14 AWG (4.0 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 10 AWG & (1) 16 AWG (4.0 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 10 AWG & (1) 18 AWG (4.0 & 0.75 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
3/8 in (10 mm):
12 & 14 AWG
(2.5 & 1.5 mm
2
)
7/16 in (11 mm):
16 & 18 AWG
(1.0 & 0.75 mm
2
)
(1-3) 12 AWG (2.5 mm
2
)
(2-3) 14 AWG (1.5 mm
2
)
(1-2) 12 AWG & (1) 14 AWG (2.5 & 1.5 mm
2
)
(1-2) 12 AWG & (1) 16 AWG (2.5 & 1.0 mm
2
)
(1-2) 14 AWG & (1) 16 AWG (1.5 & 1.0 mm
2
)
(1-2) 12 AWG & (1) 18 AWG (2.5 & 0.75 mm
2
)
(1-2) 14 AWG & (1) 18 AWG (1.5 & 0.75 mm
2
)
Wire Connector Information