User Manual
ALL PROGRAMMING IS OPTIONAL
Programming is not required for default functionality
ResetFactoryDefaults
Note:Insomeinstances,itmaybenecessarytoresetthe
xturecontrollersandconnecteddevicesbacktofactory
defaultsettings.Beforebeginning,makesurethatall
devicesareconnectedandpowered.
A
Rapidly tap the button on the xture controller three times
andholdonthefourthuntiltheLEDbeginstoashslowly;
release button.
B
Within1secondofreleasingthebutton,againrapidly
tapthebuttonthreetimesandtheLEDswillashrapidly
indicating that the unit has been reset to factory defaults.
Note:Anyassociationsorprogrammingpreviouslysetup
with the xture control will be erased and will need to be
re-programmed.
Clear Connect Wireless Fixture
Controllers
Part of the Vive Family
Limited Warranty:
http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
Troubleshooting
*
www.lutron.com
Symptom Solution
Sensordoesnotrespond
to motion.
• Sensorrequires2-minutewarmupperiodfrompowerresetbeforesensingcircuitisactive.
Defaulttimeoutis15minutes.
Lightsdonotdimorturn
ONasexpected.
• Ensurethatcontrollinesarewiredproperly
Lightsareunstableat
low-end.
• Adjustlow-endtrim.RefertoVivedocumentationonwww.lutron.com.
Customer Assistance | 1.844.LUTRON1 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 USA
Lutron,Pico,PowPak,EcoSystem,andEnergiTriPakaretrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.RadioPowrSavrandVivearetrademarksofLutronElectronicsCo.,Inc.
NECisaregisteredtrademarkoftheNationalFireProtectionAssociation,Quincy,Massachusetts.
©2017LutronElectronicsCo.,Inc.
*
For set-up, programming, and troubleshooting with a
Vive system, please refer to the installation instructions
included with the Vive hub or at
www.lutron.com
Recommended end-of-line test
1. Providepowertoxture.
2. Fixturewillgotothedriver’ssavedlevel.
3. Pressthebuttontotoggletheloadstate.LightwillfadetoON
(orOFF)over1second.GreenLEDwillstaylitfor2secondsafter
releasing the button.
4. Toggletheloadagain(ifnecessary)toensurethelightsareon.
ThiswillmakesurethelightsturnONwhenpowerisappliedthe
nexttime(atjobsite).
5. Removepower.
If testing occupancy sensor functionality:
1. Applypowertoxture.
2. Pressbutton(ifnecessary)toturnlightsoff.
3. Waitfor2minutesforsensoroccupancycircuittobecomeactive
4. Providemotioninfrontofsensor-lightswillturnON.
5. Lightswillnottunoffautomaticallyfor15minutesafterlast
motion detection.
If testing daylight sensor functionality:
1. Applypowertoxture.Fixtureshouldturnontofull(highend).If
not,pressbuttononsensor.
2. Shinelightsource(ashlight)directlyintodaylightlens.Fixture
lightwilldimdownover1minute(holdashlightsteadilyinplace).
3. Coverdaylightlens/buttonwithopaquematerial.Fixturelightwill
dimupover1minute(holdopaquematerialsteadilyinplace)