GRAFIK Eye® QS Control Unit Quick Installation and Operation Guide 13
Zone Setup (continued)
Load Type Notes
Allelectroniclow-voltage
(ELV) lighting used with an
interface must be rated for reverse
phase control dimming. Before
installing an ELV light source,
verify with the manufacturer that
their transformer can be dimmed.
When dimming, an ELV interface
(such as the PHPM-PA-DV-WH)
must be used with the control
unit.
ForallDMXorRGB/CMYDMX
lighting,anexternalDMXinterface
(suchastheQSE-CI-DMX)must
be used with the control unit.
Maximumtotallightingloadfor
Lutron® Tu-Wire® and Advance
MarkX® electronic dimming
ballasts (120 to 127 V only)
must not exceed 6 A per zone or
16 A per unit.
Zone ratings:
Notallzonesmustbeconnected;
however, connected zones must
have a minimum load:
120 - 127 V : 25 W
220 - 240 V : 40 W
Maximumzoneloads:
120 - 127 V : 800 W
220 - 240 V : 1200 W
Maximumtotallightingloadfor
magnetic low-voltage (MLV) varies
by input voltage:
120 - 127 V : 800 VA / 600 W
220 - 240 V : 1200 VA / 960 W
LUTRON
LUTRON
LUTRON
LUTRON
Setting Load Types
Direct control via
GRAFIK Eye® QS
control unit
Control via
power module or
interface
Fixture load type Choose this load type from the menu
on the GRAFIK Eye® QS control unit:
Zones
1 6
Incandescent Incandescent Power module
MLV (magnetic low-voltage) MLV Power module
ELV (electronic low-voltage) Power module
Hi-Lume
®/Eco-10® Fluorescent module
0-10 V Fluorescent module
Non-dim lighting loads Non-dim Non-dim
Neon/Cold cathode
Neon, CC Neon, CC
Tu-Wire® Tu-Wire Tu-Wire
Advance Mark X
® Tu-Wire Tu-Wire
DMX DMX
RGB/CMY DMX RGB/CMY DMX
Cree LR4/LR6 LED Cree LR4/LR6 LED Fluorescent module
Power
module or
interface