User's Manual
TouchPRO Wireless
™
P/N 041-338 Rev. A 7 69-2655EFS—01
0170 System type 1 1 heat/1 cool conventional
2 1heat/1coolheatpump(noaux.heat)
3 Heat only (2-wire systems)
4 Heat only with fan
5 HotwaterSeries20system(powertoopen&closezone
valves/normally open zone valves)
6 Coolonly
7 2heat/1coolheatpump(withaux.heat)
8 2 heat/2 cool multistage conventional
9 2 heat/1 cool multistage conventional
10 1 heat/2 cool multistage conventional
11 2heat/2coolheatpump(noaux.heat)
12 3heat/2coolheatpump(withaux.heat)
0173 Heat pump type 0 Air to air heat pump
1 Geothermalheatpump
0180 Fan control
(heating)
0 Gas/Oil heat (equipment controls heating fan)
1 Electricfurnace(thermostatcontrolsheatingfan)
0190 Changeover valve
(O/B terminal)
0 O/B terminal controls valve in cooling
1 O/Bterminalcontrolsvalveinheating
0200 Auxiliary Heat 0 Electric backup heat
1 Fossil fuel backup heat
0210 External Fossil Fuel
Kit
0 None
1 Yes
0220 1st Stage Cool/
Compressor cycle
rate
3 Recommended for most compressors
[otheroptions:1,2,4,5,or6CPH]
0230 2nd Stage Cool/
Compressor cycle
rate
3 Recommended for most compressors
[otheroptions:1,2,4,5,or6CPH]
0240 First stage heat
cycle rate (CPH=
cycles per hour)
5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hotwatersystems&furnacesof90%+efciency
9 Electricfurnaces
[Otheroptions:2,4,6,7,8,10,11,12CPH]
0250 Second stage heat
cycle rate (CPH)
5 Gas or oil furnaces of less than 90% efficiency
1 Steam or gravity systems
3 Hotwatersystems&furnacesof90%+efciency
9 Electricfurnaces
[Otheroptions:2,4,6,7,8,10,11,12CPH]
0260 Third stage heat
cycle rate (CPH)
9 Electric auxilliary heat
1 Steam or gravity systems
3 Hotwatersystems&furnacesof90%+efciency
5 Gasoroilfurnacesoflessthan90%efciency
[Otheroptions:2,4,6,7,8,10,11,12CPH]
0280 Backlight 0 Backlight ON for approx. 8 seconds after keypress
1 Backlightalwaysonlowintensity,fullbrightafter
keypress
Setup functions Settings & Options (factory default in bold)
Installer setup
Continuedonnextpage