Installation Guide

FIGURE 2
LIGHTING
FIXTURE
(+) LINE
(-) COMMON
(+)DIM V+
BLACK
WHITE
PURPLE
GROUND
GRAY
YELLOW
GROUND
(-)DIM V-
0-10V DIMMABLE WIRING METHOD:
Universal voltage driver permits operation at 120V through 277V, 50 or 60
Hz. For 0-10V Dimming, follow the wiring directions as in figure 2
1. Connect the GROUND wire from fixture to supply ground
2. Connect the white fixture lead to the (-) COMMON supply lead
3. Connect the black fixture lead to the (+) LINE supply lead
4. Connect the purple fixture lead to the (V+) DIM lead
5. Connect the gray fixture lead to the (V-) DIM lead
5. Cap the yellow fixture lead, if present. DO NOT connect
6. If you do not require the dimming feature keep the purple and gray lead
capped and unconnected.
TROUBLESHOOTING:
1. Check that the line voltage at fixture is correct
2. Is there voltage at the lamp fixture wires? If there is no voltage, check
all connections
3. Ensure that the fixture is grounded properly