Owner's manual

BoilerSpection HD/SD Manual Troubleshooting 41
5.4 Retraction/Filtration
Symptom Probable Cause Corrective Action
Immediate retraction Loss of air, air pressure caused by site
supply failure
Check supply of air and power
Failure to retract Mechanical failure of the retraction
system
Check mechanical fittings and
enclosure for loose or out of
place components and repair
Lens failure due to heat.
Melts within boiler
Replace or service lens
Damage to camera/lens Poorly tuned retraction forces
damaged to the system
Service broken components or
properly tune retraction
system to avoid future damage
Loss of air pressure Clogged filter caused filter failure
within the filtration unit
Replace Air filters
Failure of Vortex
Cooling
Premature failure of
filtering
Excessive heat to the filter system
caused by the environment
Consider adding shielding to
reduce the air filters
environmental exposure
Auto retracts, loss of
image
Site power failure Verify and replace failed
component
Short Circuits, loss of
image
Water damage Verify and replace failed
component
5.5 Field Enclosures
Symptom Probable Cause Corrective Action
Loss of image Communication failures ie. Ethernet
failure, connections/switch failure
Open circuit breakers and
check all power wiring
connetions
Power failure to cabinet Check integrity of input power
supply
Communication failure due to
mechanical vibrations
Check mechanical fittings and
enclosure for loose or out of
place components and repair
Cabinet left open causing
heat/water/dust in affect components
Verify and replace failed
component
Power surges Site supply issues causing circuit
breakers to trip
Check integrity of input power
supply