Instructions / Assembly
2
Installation Instructions - Crosstour MAXX
INSTALLATION
BACK BOX INSTALLATION
1. Unscrew door with Phillips screw driver. Remove door
from back box.
2. Place inverted back box on solid surface. Using a 9/32”
bit, drill out the four mounting holes. (Figure 1.)
3.  Over Junction Box Wiring And Rear Entry Conduit
Installation: Loosen But DO NOT remove two screws
securing wire-way cover plate (Figure 2). Rotate
wire-way cover plate counterclockwise and remove
wire-way cover plate from opening. Do not remove the
wire-way cover plate for thru-branch wiring.
ote:N Use drill dimensions (Figure 3.) to mark drill location. 
DO NOT use back box as the drill guide. Drill four 
holes into wall surface. Secure back box to wall with 
1/4” lag bolts and washers into anchors (anchors  
supplied by others). Maximum allowable diameter 
for lag bolt is 1/4”. Installer must apply silicone 
compound around entire perimeter of the back box 
where it mates to the mounting surface. This will 
create a water-tight seal between the mounting 
surface and the back box.
ELECTRICAL CONNECTIONS
4.   Over Junction Box: Make supply wiring connections to
the backside of the wire-way cover plate. Follow NEC 
guidelines for wet location wiring (wire nuts supplied by 
others). Ensure all wires are secured in the junction box 
and re-install wire-way cover plate by rotating clockwise 
into the screws. Tighten wire-way cover plate screws to 
10 in-lbs. (Figure 2).  
Thru-Branch Conduit: Remove the required 1/2” NPT 
conduit plug(s). Apply sealing compound or Teflon 
tape to liquid tight conduit fitting (supplied by others) 
entering back box to create water tight seal. DO NOT 
remove the wire-way cover plate (Figure 2). Remove 
wire leads from the wire way cover plate by gently 
pulling the wiring located in the black grommet toward 
you. DO NOT remove black grommet from the  
wire-way cover plate. 
 Back Conduit Entry: Remove the black grommet and 
wires from the wire-way cover plate (DO NOT remove 
circular gasket). Attach conduit to wire-way cover plate 
with watertight connector. Re-install wire-way cover 
plate by rotating clockwise into the screws. Tighten 
wire-way cover plate screws to 10 in-lbs. (Figure 2).
5.  Secure door into lock hinges located at the top of the
back box (for down light illumination) (Figure 4). Utilize
Push-in connectors to make fixture-wiring connections
(see wiring diagrams).
Wall Gasket
(4) Mounting
Holes
(2) Cover
Plate Screws
Black 
Grommet
Black 
Grommet
Wire-Way 
Cover Plate
Push-in 
Connectors
Circular 
Gasket
(Back view)
Wire-Way Cover Plate
Back View of Back BoxTest Button
Figure 1. 
Figure 2. 
Figure 3. 
5"
(4) Mounting
Holes
Access Outlet Box
5”
5-5/8”
2-13/16”
2-1/2”
5622H01
THIS SIDE IN FIXTURE
SEE INSTRUCTION FOR 
CONDUIT APPLICATION
THIS SIDE IN FIXTURE
SEE INSTRUCTION FOR 
CONDUIT APPLICATION
COOPER LIGHTING SOLUTIONS  IB514001EN    Installation instructions