- Site Preparation, Installation and Operator's Manual for Lucent Technologies Series 1 Uninterruptible Power Systems


Lucent Technologies Model 3000 UPS Operator's Manual (167Ć405Ć119 Issue 3)

  
Input Voltage Range 160 to 276 Vac
Bypass Isolation Module
Input Voltage Range
187 to 276 Vac
Input Power Factor 0.95 Typical
Frequency Range 50/60 Hz 3Hz
Surge Protection IEC 801Ć4
Output Wave Form Sine wave
Output Voltage (without
Bypass Module)
200/208/220/230/240 Vac 3%
Common Mode Noise
Rejection
>60 dB @ 100 kHz
Transverse Mode Noise
Rejection
>80 dB @ 100 kHz
Input Cord Detachable 2Ćmeter cord with L6Ć30P
Outlets (UPS Module) IEC 320 (1)
Output Voltages and Outlets
(with BDM)
120/208V: L6Ć30R or L14Ć30R, 4x5Ć15R
120/240V: L6Ć30R or L14Ć30R, 4x5Ć15R
120: L5Ć30R, 4x5Ć15R
208V Hardwired: 120/208V
240V Hardwired: 120/240V
Output Voltages and Outlets
(with BIM)
(208V available with Model 2500 only)
220/230/240V: 1 x IEC 320ĆC19
3 x IEC 320ĆC13
220/230/240V Hardwired: 220/230/240V
Batteries (10) per Module 12 Vdc, 5 Ah, maintenanceĆfree rechargeable lead acid
Battery Module 120 Vdc
Operating Environment Temperature:10°Cto40°C
(50°Fto104°F)
Humidity: 5 to 95%
(noncondensing)
Agency Approvals Safety: EN50091Ć1
UL 1778
cUL
EMC: FCC Part 15 Class A
EN50091Ć2