Maintenance Object Repair Procedures 
Page 10-222CABINET (Cabinet Sensors) 
10
2FAIL
(cont’d.)
4. Check the temperature at the top of the cabinet. If the temperature is 
at least 65
0 
C (149
0 
F), the ambient room temperature is too high, and 
the fans cannot cool the system. Unless the room temperature is 
reduced, the system is going to shut down soon. If the temperature is 
less than 65
0 
C, then:
a. The PR-MAINT (Maintenance/Tape Processor), DUPINT 
(Duplication Interface) circuit pack, or the EPN MAINT 
(Maintenance) circuit pack may be incorrectly reporting this 
condition. First, look for and resolve all errors on these MOs, then 
rerun the test. If this test fails again, return to Step 1. If there are no 
errors, continue.
b. The sensor S1 may be incorrectly reporting the temperature at the 
top of the cabinet. Replace sensor S1, and rerun the test. If the test 
still fails, escalate the problem.
3 FAIL The AHD1 circuit pack has reported both air flow and temperature 
problems. Resolve the airflow error first, then, correct the temperature 
error as described previously.
PASS The AHD1 circuit pack has not reported any temperature or air flow 
problems. The temperatures at the air exhaust at the top of the cabinet and 
the air intake at the bottom of the cabinet can be measured and the results 
compared against the criteria described previously. If a problem has been 
reported, troubleshoot this problem by using the procedures for the "FAIL" 
cases described previously.
Table 10-76. TEST #122 Cabinet Temperature Query Test 
[Non-Variable Speed Fans] — Continued
Error 
Code
Test 
Result Description/ Recommendation