User manual
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si 
555-230-127  
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-216CABINET (Cabinet Sensors) 
10
10. Replace the fan assembly cover or panel.
Hardware Error Log Entries and Test to Clear 
Values
System Technician-Demanded Tests: 
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when 
inspecting errors in the system. By clearing error codes associated with the 
Battery & Battery Charger Query Test
, for example, you may also clear errors 
generated from other tests in the testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the 
appropriate test description and follow the recommended procedures.
Cabinet Sensors Error Log Entries
Error 
Type
Aux 
Data Associated Test
Alarm 
Level
On/Off 
Board Test to Clear Value
0
1
0 Any Any Any test environment P sh r 1
1 Any Cabinet Temperature 
Query Test (#122)
MINOR ON test environment P sh r 3
257 Any Cabinet Temperature 
Query Test (#122)
MAJOR ON test environment P sh r 3
Table 10-75. System Technician-Demanded Tests: CABINET
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence D/ND
1
Battery & Battery Charger Query Test (#5) (a) X X ND
AC Power Query Test (#78) (b) X X ND
Power Unit Query Test (carrier E) (#127) (c) X X ND
Power Unit Query Test (carrier D) (#127) (c) X X ND
Power Unit Query Test (carrier A) (#127) (c) X X ND
Power Unit Query Test (carrier B) (#127) (c) X X ND
Power Unit Query Test (carrier C) (#127) (c) X X ND
Emergency Transfer Query Test (#124) (d) X X ND
Cabinet Temperature Query Test (#122) X X ND