Page 10-210CABINET (Cabinet Sensors) 
10
are wired in parallel with a rear fan. The repair scenarios that follow rely on the 
technician’s ability to distinguish between high fan speed and low fan speed. The 
only way to distinguish between the fan speeds is by the sound of the fans. When 
operating at high speed, the fans make a higher pitched sound than when they 
run at low speed. The technician probably knows from prior experience what the 
fans sound like at low speed as well as at high speed.
Figure 10-10 shows a multicarrier cabinet system and the location of the 
temperature sensors S1 through S4 (there are actually two S3 sensors and two 
S4 sensors) as well as the location of the fans, the AHD1 circuit pack, and the 
filters. The figure also shows other environment-related components of a 
multicarrier cabinet system and can be ignored for this section on Cabinet 
Sensors.