User manual
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si 
555-230-127  
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-1335TDM-CLK (TDM Bus Clock) 
10
Notes:
a. The Tone-Clock circuit pack may have a clock at the edge of its specified 
frequency. This can cause Expansion Interface circuit packs and SNI 
circuit packs to go out-of-frame or report no-neighbor conditions. This can 
is turn cause EPNs, Expansion Archangel Links (EALs), Remote Neighbor 
Links (RNLs), and/or Local Neighbor Links LNLs) to go down. When this 
error is alarmed, Clock Health Inquiry Test (#46) will fail with an error code 
of 1.
1. Replace the Tone-Clock circuit pack identified in the error log. See 
How to Replace the Tone-Clock Circuit Pack
 in the TONE-BD 
section.
b. The indicated Tone-Clock circuit pack has been made unavailable via the 
busyout tone-clock UUC command. It only applies to systems which 
have the High or Critical Reliability Option administered, because only a 
standby Tone-Clock circuit pack may be made busy by that command. To 
resolve this error, execute the release tone-clock UUC command for the 
alarmed circuit pack.
c. This error type indicates that the circuit pack has been removed or has 
been insane for more than 11 minutes. To clear the error, reinsert or 
replace the circuit pack.
1. As a general rule, any 
on board
 errors against the TDM Bus Clock should be resolved before 
pursuing any other errors against SPE or PNC components. 
Off board
 clock errors may be caused 
by other board errors, and should usually be addressed once any on board errors have been 
resolved.
2. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
3. Major or Minor alarms on this MO may have been downgraded to Warning alarms based on the
values used in the set options command.
1281(h)
1282(h)
Any None MINOR OFF
1537 Any Clock PPM 
Inquiry(#150)
test tone-clock UUC sh
2049(i) Any Standby 
Reference Health 
Check Test(#651)
MAJOR
3
ON test tone-clock UUC
2305(j) 0 None WARNING OFF
Table 10-464. TDM Bus Clock Error Log Entries  — Continued
Error 
Type
Aux 
Data Associated Test
Alarm 
Level
On/Off 
Board
1
Test to Clear Value
Continued on next page