Page 10-1100RING-GEN (Analog Ring Generator) 
10
Table 10-391. TEST #118 Analog Ring Generator Query Test 
Error 
Code
Test 
Result Description/ Recommendation
1
1000 
1001 
1003 
1115 
2012 
2100
ABORT Could not seize the resources to run the test. Other maintenance is running 
on the active tone/clock circuit pack.
1. Wait for the green LED on the active tone/clock circuit pack to go out; 
(use the status port-network command to determine the Active 
tone/clock circuit pack). 
2. Rerun the test. If the test aborts again, refer to TDM-CLK (TDM Bus 
Clock) Maintenance documentation.
2000 ABORT Response to the request was not received within the allowable time period.
1. Look for TDM-CLK errors and alarms. Resolve all other tone/clock 
problems first.
2. Rerun the test.
1005 ABORT The tone/clock is unable to read the analog ringing voltage level when the 
tone/clock is in the Processor Interface slot. This test is not available for the 
Processor Port Network in this configuration.
FAIL Ringing voltage is below acceptable levels.
PROCEDURE FOR A MULTI-CARRIER CABINET SYSTEM.
1. If this is a High or Critical Reliability system, determine the active 
Tone-Clock circuit pack by issuing a status port network command. 
Make the Standby Tone-Clock circuit pack active via the set 
tone-clock PC command and rerun the test.
a. If the test passes, the trouble is with the new Standby Tone-Clock 
circuit pack. Refer to the TONE-BD (Tone-Clock Circuit Pack) 
Maintenance documentation for details on replacing the Standby 
Tone-Clock circuit pack. After the circuit pack is replaced, make 
this Tone-Clock active again by issuing the set tone-clock PC 
command and rerun the test.
b. If the test fails, then proceed with Step 2.
2. Look for and resolve CARR-POW (Carrier Port Power Supply Unit) 
alarms first, and then rerun the test.
3. Check fuse F9 on the Power Distribution Unit. Replace F9 if it is blown, 
and rerun the test. If the test still fails, then an Analog Line circuit pack 
could be defective and causing the Analog Ring Generator and/or 
fuse F9 to fail.
4. Unseat all Analog circuit packs in the affected cabinet, and replace 
fuse F9 again if needed. Rerun the test.
Continued on next page