User manual
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si 
555-230-127  
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-1033POWER (Battery & Battery Charger for DC-Powered Systems 
10
Notes:
a. Refer to “AC-POWER” (AC Power) for a description of this test.
b. Refer to “EMG-XFER” (Emergency Transfer) for a description of this test.
c. Refer to “CABINET” (Cabinet Sensors) for a description of this test.
d. Refer to “EXT-DEV” (External Alarm) for a description of this test.
e. Refer to “RING-GEN” for a description of this test.
NOTE:
This test shows up in the test sequence only if there is a TN768 or 
TN780 Tone-Clock circuit pack in the port network being tested.
Battery & Battery Charger Query Test (#5)
This test queries the Maintenance/Tape Processor in a standard PPN, the 
Duplication Interface circuit pack in a PPN for a High or Critical Reliability 
system, or the EPN Maintenance circuit pack in an EPN for the status of the 
battery pack and battery charger, and reports the result. In a DC-powered 
system, this test should never fail. During this test, the status LED on the battery 
charger is lit and extinguished if the status of the battery charger is reported as 
normal. This event is a result of checking that the battery charger is connected.
Table 10-352. TEST #5 Battery & Battery Charger Query Test 
Error 
Code
Test 
Result Description/ Recommendation
1000 ABORT System resources required to run this test are not available.
1. Retry the command at 1-minute intervals a maximum of 5 times.
1005 ABORT Battery charger is not connected since the system uses DC power and the 
battery charger and battery are for AC-powered systems.
1. Ignore this error in DC-powered systems.
2000 ABORT Response to the test request was not received within the allowable time 
period.
2028 ABORT Internal system error prevented the extinguishing of the Battery Charger 
status LED.
1. Although this test is not relevant for DC-powered systems, this error 
should trigger close monitoring of the system as this error means that 
internal system problems exist.
2029 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
Continued on next page