User manual
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si 
555-230-127  
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-1030POWER (Battery & Battery Charger) for AC-Powered Systems 
10
e. If you have an alarm and all LEDs are ok (PWR OK and BOK) on the 
rectifier modules, and the BIU (Battery Interface Unit), make sure the 
BIU and the RM0850 rectifiers are seated properly (plugged in). If the 
BOK LED on the BIU is ok use the following information to check the 
number of rectifiers serving this cabinet:
Number of carriers    Number of rectifiers
per cabinet         per cabinet
----------------------------|---------------------------------
1                 2
2                 3
3                 3
4                 4
5                 4
If the number of rectifiers is correct replace the maintenance circuit pack 
in the EPN or PPN.
4. If the test still fails, then follow normal escalation procedures.
10 FAIL This indicates that Error Codes 2 and 8 have occurred. Refer to these 
descriptions. Also, refer to the description for Error Code 14 for this test.
12 FAIL This indicates that Error Codes 4 and 8 have occurred. Refer to these 
descriptions. Also, refer to the description for Error Code 14 for this test.
14 FAIL This indicates that Error Codes 2, 4, and 8 have occurred. Refer to these 
descriptions.
NOTE:
This could also indicate that the detection logic on the DUPINT 
(Duplication Interface), PR-MAINT (Maintenance/Tape Processor), or 
EPN MAINT (Maintenance) circuit pack is defective. Such an error will 
not be detected by the respective maintenance. If many environment 
tests are failing, replace the suspect circuit pack (depending on system 
configuration).
PASS The Maintenance/Tape Processor in a multicarrier cabinet PPN system without 
High or Critical Reliability, the Duplication Interface circuit pack in a PPN for a 
High or Critical Reliability system, or the EPN Maintenance circuit pack in an 
EPN have reported that the status of Battery & Battery Charger is good.
Table 10-350. TEST #5 Battery & Battery Charger Query Test — Continued
Error 
Code
Test 
Result Description/ Recommendation
Continued on next page