User manual
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si 
555-230-127  
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-613EXP-INTF (Expansion Interface Circuit Pack) 
10
s. Error Type 10001 is a report that the EI circuit pack dropped one control 
message to the EPN. This condition may have been observed as a call 
that did not complete correctly. No system technician action is required.
t. In response to Error Type 10002, the system denied all calling services for 
up to 10 seconds.
If EI Error Type 257 is logged at the same time against an Expansion 
Interface circuit pack on this link, first try to resolve this error. The error 
associated with Error Type 257 could be the cause of this error.
If Error Type 257 is not logged at the same time as this error, then Error 
Type 10002 indicates that heavy call traffic was encountered involving 
EPN endpoints.
No system technician action is required; however, should this error recur 
frequently, the system should be examined for traffic engineering. The 
PPN and EPNs may not be equipped with sufficient trunks and Tone 
Detectors for the number of stations in each cabinet.
u. Error Type 10003 indicates that heavy call traffic involving EPN endpoints 
has returned to normal levels. This Error Type should always appear after 
Error Type 10002 or 10004. No system technician action is required.
v. Error type 10004 indicates that an extreme backup of traffic was present 
on the EI circuit pack. The EPN served by this link was most probably not 
providing service when this error was logged. If this is a high or critical 
reliability system, the system should have switched to the Standby 
Expansion Link in order to restore service. Error type 11000 with an Aux 
value of 5 should have been logged against EXP-INTF to indicate this 
condition.
In a standard system, the system should have reset the EPN in order to 
restore service. EXP-LINK Error Type 122 with an Aux value of 6 should 
have been logged to indicate this condition.
w. Error Type 11000 with an Aux value of 0 appears when an EI Link switch 
takes place. Data calls between the PPN and EPN may have experienced 
some data loss or, in severe cases, the data calls may have dropped. The 
link that became active is the link with the circuit pack address given in the 
Error Log entry. The link switch may have occurred for several reasons:
1. System Technician demanded the Expansion Interface Link switch. 
This can be verified by using the list history command.
2. The Expansion Interface Link switch may have been scheduled. 
Check the Maintenance-Related System Parameters form.
3. An Expansion Interface circuit pack error may have been detected. 
Examine the Error Log for other EI circuit pack errors with the same 
approximate time as this error.
4. An EPN Maintenance circuit pack error may have been detected. 
Examine the Error Log for MAINT errors with the same approximate 
time as this error. MAINT Error Type 2561 indicates that the Active 
Expansion Interface circuit pack on the EPN could not 