User manual
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si 
555-230-127  
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-584EMG-XFER 
10
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests: 
Descriptions and Error Codes
Always investigate tests in the order presented in the following tables. By 
clearing error codes associated with the 
Battery & Battery Charger Query Test,
for example, you may also clear errors generated from other tests in the testing 
sequence. For example, you may also clear errors generated from other tests in 
the testing sequence.
Single Carrier System
Notes:
a. Refer to “DC-POWER” for a description of this test.
b. Refer to “EXT-DEV” for a description of this test.
c. Refer to “RING-GEN” for a description of this test.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the 
appropriate test description and follow the recommended procedures.
1. D = Destructive; ND = Nondestructive
Table 10-200. Emergency Transfer Error Log Entries
Error 
Type
Aux 
Data Associated Test
Alarm 
Level
On/Off 
Board Test to Clear Value
0
1
0 Any Any Any test environment P sh r 1
1 Any Emergency Transfer 
Query (#124)
MAJOR ON test environment P r 3
257 0 Emergency Transfer 
Query (#124)
WARNING ON test environment P r 3
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence D/ND
1
Power Query Test (#79) (a) X X ND
Emergency Transfer Query Test (#124) X X ND
External Alarm Lead Query Test (#120) (b) X X ND
Analog Ring Generator Initialization Test (#117) (c) X X ND
Analog Ring Generator Query Test (#118) (c) X X ND