User manual
DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si 
555-230-127  
Issue 1
August 1997
Maintenance Object Repair Procedures 
Page 10-380DAT-LINE (Data Line) 
10
Error Log Entries and Test to Clear Value
s
Notes:
a. This is a software audit error that does not indicate any hardware 
malfunction. Run the Short Test Sequence and investigate errors (if any).
b. This error type indicates that the circuit pack has been removed or has 
been insane for more than 11 minutes. To clear the error, reinsert or 
replace the circuit pack.
c. This error is logged when the Data Line circuit pack finds an error with the 
transmit/receive circuitry of an administered Data Line on circuit pack 
insertion. Perform the following procedure:
1. Issue the busyout board PCSS command to busyout the Data Line 
circuit pack on which this port resides.
2. Issue the reset board PCSS command. Check the Hardware Error 
Log to determine if Error Type 769 is logged again for the DAT-LINE 
MO.
NOTE:
When displaying errors, set the Active Alarms Only field to "n."
If Error Type 769 reappears, replace the DAT-LINE circuit pack. If 
Error Type 769 does not reappear, proceed to Step 3.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the appropriate 
test description and follow the recommended procedures.
Table 10-121. Data Line Error Log Entries
Error 
Type
Aux 
Data Associated Test Alarm Level
On/Off 
Board Test to Clear Value
0
1
0 Any Any Any test port PCSSpp sh r 1
1 Digital Loop Around 
Test (#171)
MINOR ON test port PCSSpp sh r 2
15(a) Any Audit Update Test 
(#36)
18 0 busyout port PCSSpp WARNING OFF release port PCSSpp
130 (b) None WARNING ON test port PCSSpp sh
257 Conference Circuit 
Test (#7)
MINOR ON test port PCSSpp l r 2
513 NPE Crosstalk Test 
(#6)
MINOR ON test port PCSSpp l r 2
769(a) Any (c) None