Maintenance Object Repair Procedures 
Page 10-1307STRAT-3 (Stratum 3 Clock)] 
10
32 FAIL All clock unit(s) failed.
1. Look at the Stratum 3 cabinet for red LEDs on circuit 
cards marked "ST3." Replace the card(s).
2. Determine if the alarm still exists by issuing the test 
synchronization r 4 command to clear the alarm. If 
any test repetitions fail, follow the procedure for 
those failures. If the problem persists after you have 
performed this procedure three times, follow normal 
escalation procedures.
2101 FAIL The TN780 Tone-Clock circuit pack detects loss of 
signal. Refer to Note (b) of the STRAT-3 Hardware Error 
Log Entries table in the STRAT-3 (Stratum 3 Clock) 
Maintenance documentation for replacement 
procedures.
PASS The Stratum 3 clock has reported that it has no alarm 
conditions. If synchronization problems have been 
reported, look for SYNC errors and refer to SYNC 
(Synchronization) Maintenance documentation for 
recommended strategy for those errors.
Table 10-394. TEST #649 Stratum 3 Clock Alarm Query — Continued
Error 
Code
Test 
Result Description/ Recommendation
Continued on next page