User Guide
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si 
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1270STBY-SPE (Standby SPE) 
10
labeled "standby" on the status system form, wait 20 minutes. This does 
not include cases where the command completes with the terminal 
message line errors "Refresh not successful; use ‘display errors’ to check 
for STBY-SPE errors" or "Cannot interrupt Standby SPE while entering 
maintenance mode; please try later". Issue the refresh spe-standby 
command once more. If the Standby SPE is not labeled "standby" on the 
status system form after this attempt, use the busyout spe-standby 
command.
■ reset spe-standby <level> 
Normally, when the standby is brought into maintenance mode, it is done 
so with a Warm Restart. The reset spe-standby command can be used to 
bring the standby SPE from standby mode into maintenance mode with 
the requested restart level.
■ reset system-interchange <health-override> 
If the health-override option is NOT specified, and if the standby Fault 
Severity Level (FSL) is less than or equal to that of the active SPE, and if 
the standby SPE is in standby mode, the interchange is allowed. Actually, 
if the standby FSL is less than that of the active FSL, the system does its 
own interchange in due time. If the FSL of the standby SPE is higher than 
that of the active SPE, but the alarmed standby maintenance objects do 
not affect the ability of the standby SPE to be put into standby mode, the 
command is rejected. This indicates that the health-override option can be 
used. If there are problems that would prevent the standby SPE from 
running system software, the command is rejected outright.
If the health-override option is specified, and if the standby SPE is in 
standby mode, a Hot interchange is performed, regardless of the FSL 
level of the two SPEs. Once the interchange is performed, if the new active 
FSL is higher than the standby FSL, a STBY-SPE warning alarm is raised 
against the new standby SPE. This indicates that the system was forced to 
switch SPEs and is currently being held on the active SPE artificially. This 
prevents a SPE interchange back to the original active SPE. This 
STBY-SPE warning alarm lasts for one hour. After this time passes, system 
switches to the SPE with the lowest FSL.
The STBY-SPE alarm is also retired if there is some indication of system 
technician testing of the standby SPE before the one hour expires. The 
assumption here is that a system technician person is present because 
the health-override option was used. Therefore, if there is some indication 
that repair work is going on, the alarm generated by the health-override 
should be retired. The following are indications of system technician 
testing being done: the standby SPE is busied out and then released, the 
active SPE is hard selected via the switches, or a test spe-standby long 
command is performed.
■ test processor [1] a|b [short | long] 
Runs the same set of tests on the standby SPE as on the Active SPE. Refer 
to the PROCR-BD and PR-MAINT sections for a complete list of the tests 
that are run.










