Maintenance Object Repair Procedures 
Page 10-1247SHDW-LNK (Memory Shadowing Link) 
10
2049 
(cont’d.)
FAIL
(cont’d.)
8. Issue the display errors command and check to see if an Error Type 
58 is logged against STBY-SPE. If an Error Type 58 is logged OR if no 
error types are logged against STBY-SPE, the problem is either the 
Standby SPE Processor circuit pack, or the Standby SPE Memory 
circuit pack, or the carrier B Duplication-Interface circuit pack, or the 
carrier A Duplication-Interface circuit pack.
■ If the red LED on the Standby SPE Processor circuit pack is on and 
the Standby SPE Processor circuit pack has not been replaced yet, 
replace the Standby SPE Processor circuit pack as described in 
Chapter 6 and proceed with Steps 9, 10, and 11. If the red LED on 
the Standby SPE Processor circuit pack is on and the Standby SPE 
Processor circuit pack has been replaced, replace the Standby SPE 
Memory circuit pack as described in Chapter 6 and proceed with 
Steps 9, 10, and 11.
■ If the red LED on the Standby SPE Memory circuit pack is lit, 
replace the Standby SPE Memory circuit pack as described in 
Chapter 6 and proceed with Steps 9, 10, and 11.
■ If the red LED on the Standby SPE Duplication Interface circuit pack 
is lit, replace the Standby SPE Duplication Interface circuit pack as 
described in Chapter 6 and proceed with Steps 9, 10, and 11.
■ If the red LED on the Active SPE Duplication Interface circuit pack is 
lit, replace the Active SPE Duplication Interface circuit pack as 
described in Chapter 6 and proceed with Steps 9, 10, and 11.
NOTE:
The Duplication Interface circuit pack must be made to reside in the 
Standby SPE before it can be replaced.
Table 10-388. TEST #318 Shadow Link Test  — Continued
Error 
Code
Test 
Result Description/ Recommendation
Continued on next page