Maintenance Object Repair Procedures 
Page 10-1200RING-GEN (Analog Ring Generator) 
10
Hardware Error Log Entries and Test to Clear 
Values
System Technician-Demanded Tests: 
Descriptions and Error Codes
Always investigate tests in the order presented in the following tables when 
inspecting errors in the system. By clearing error codes associated with the 
Analog Ring Generator Initialization Test
, for example, you may also clear errors 
generated from other tests in the testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the appropriate 
test description and follow the recommended procedures.
1. D = Destructive; ND = Nondestructive
Analog Ring Generator Error Log Entries
Error 
Type
Aux 
Data Associated Test
Alarm 
Level
On/Off 
Board Test to Clear Value
0
1
0 Any Any Any test environment UU
1 Analog Ring Generator Query 
Test (#118)
MAJOR ON test environment UU r 3
Multicarrier Cabinet
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence D/ND
1
Analog Ring Generator Initialization Test (#117) X X ND
Analog Ring Generator Query Test (#118) X X ND
Battery & Battery Charger Query Test (#5) (a) X X ND
AC Power Query Test (#78) (b) X X ND
Power Unit Query Test (Carrier E) (#127) (c) X X ND
Power Unit Query Test (Carrier D) (#127) (c) X X ND
Power Unit Query Test (Carrier A) (#127) (c) X X ND
Power Unit Query Test (Carrier B) (#127) (c) X X ND
Power Unit Query Test (Carrier C) (#127) (c) X X ND
Emergency Transfer Query Test (#124) (d) X X ND
Cabinet Sensors Query Test (#122) (e) X X ND
External Alarm Lead Query Test (#120) (f) X X ND