User Guide
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si 
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-1176PRI-CDR/SEC-CDR (PRI-CDR Link) 
10
the extension number in Alt Name field of Hardware Error Log and refer to 
XXX-BD (Common Port Circuit Pack) Maintenance documentation for 
resolutions.
If the destination is "eia," then look for PR-MAINT errors in the Hardware 
Error Log. If present, refer to PR-MAINT (Maintenance/Tape Processor) 
Maintenance documentation.
4. Is a data channel on TN777 Network Control circuit pack in the 
in-service/idle state?
Enter list data command and find out the extension numbers of data 
channels on TN777 Network Control circuit pack. Enter status data 
extension command and make sure that at least one data channel is in 
the in-service/idle state. If no data channel is available, then look for 
DATA-CHL/DATA-CON/DATA-BD errors in the Hardware Error Log. If 
present, refer to DATA-BD (Network Control Circuit Pack).
5. Is the external CDR output device available?
Make sure that the CDR output device is on-line and ready for service. 
Check the physical connectivity between Data Module and the CDR 
output device or between the EIA port on backplane of the switch and the 
CDR output device.
It is recommended to busy out the CDR link before executing maintenance tests 
over the CDR link. If the CDR link is busied out, then all CDR link maintenance 
actions are deactivated. The interference to tests of other MO is off.