Maintenance Object Repair Procedures 
Page 10-1131POWER (Battery & Battery Charger) for AC-Powered Systems 
10
8FAIL
NOTE:
For a Global AC MCC (J58890CH) use the 
procedures outlined in step 3.
There is a reserve power fault. A problem exists with the 
battery charger (more probable) or the battery (less 
probable).
1. Replace the battery charger or the battery. The fault 
should disappear. However, the test fails with Error 
Code 4 if the battery is charging.
!
WARNING:
Always turn off the battery charger before 
replacing the batteries.
2. Rerun the test. If the test still fails with an error code 
other than 4 (that is, there is something wrong 
besides the battery needing charging), the 
PR-MAINT (Maintenance/Tape Processor) in a 
multicarrier cabinet PPN system without High or 
Critical Reliability, the DUPINT (Duplication 
Interface) circuit pack in a PPN for a High or Critical 
Reliability, or the EPN MAINT (Maintenance) circuit 
pack in an EPN could be reporting this condition 
incorrectly. Resolve all alarms on these MOs and 
rerun the test. There are failures that can occur on 
the Maintenance/Tape Processor, Duplication 
Interface, and EPN Maintenance circuit pack that 
ARE NOT be detected by the respective 
maintenance, but that cause many, if not all, 
environment tests to fail. If many environment tests 
are failing, the suspect circuit pack, depending on 
the system configuration, should be replaced and 
the test rerun. If the test still fails, then follow normal 
escalation procedures.
Table 10-332. TEST #5 Battery & Battery Charger Query Test — Continued
Error 
Code
Test 
Result Description/ Recommendation
Continued on next page