DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si 
555-230-123
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-984OPS-LINE (DS1 OPS Line) 
10
Hardware Error Log Entries and Test to Clear 
Values
Notes:
a. This is a software audit error that does not indicate any hardware 
malfunction. Run the Short Test Sequence and investigate associated 
errors (if any).
b. The DS1OPS Line has been busied out by a busyout station <ext> 
command. No calls can be made on this line.
c. This error type indicates that the circuit pack has been removed or has 
been insane for more than 11 minutes. To clear the error, reinsert or 
replace the circuit pack.
d. Error Type 1793 indicates a problem with the DS1 Interface circuit pack. 
Since there is no error against the OPS-LINE port, no alarm is raised 
against the OPS-LINE port. However, there should be errors logged 
against the DS1 Interface circuit pack. Look for DS1-BD errors in the 
Hardware Error Log and follow procedures provided in the DS1-BD (DS1 
Interface Circuit Pack) Maintenance documentation.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the 
appropriate test description and follow the recommended procedures.
DS1 OPS Maintenance Error Log Entries
Error 
Type
Aux 
Data Associated Test
Alarm 
Level
On/Off 
Board Test to Clear Value
0
1
0 Any Any Any test station <ext> sh r 1
15 (a) Any Audit and Update 
Test (#36)
18 (b) 0 busyout station 
<ext>
WARNING OFF release station <ext>
130 (c) None WARNING ON test station <ext>
1281 Conference Circuit 
Test (#7)
MINOR ON test station <ext> l
1537 NPE Crosstalk Test 
(#6)
MINOR ON test station <ext> l
1793 (d) test circuit pack PCSS l