User Guide
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si 
555-230-123 
Issue 1
April 1997
Routine Maintenance Procedures 
Page 5-72Install DS1 CPE Loopback Jack (T1 Only) 
5
NOTE:
The loss of signal (LOS) alarm (demand test #138) is not processed 
during this test while the 3-in-24 pattern is active.
5. Enter clear meas ds1 loop <location> to clear the bit error count.
6. Enter clear meas ds1 log <location> to clear the performance 
measurement counts.
7. Enter clear meas ds1 esf <location> to clear the ESF error count.
8. Enter list meas ds1 sum <location> to display the bit error count. Refer 
to Table 5-5
 for troubleshooting information. 
Table 5-5. DS1 Span Troubleshooting
Displayed 
Field Function Indication
Test: cpe- 
loopback-jack
Pattern 3-in-24 The loopback jack test is active.
Synchronized Y or N If “y” displays, the DS1 circuit pack has 
synchronized to the looped 3-in-24 pattern and is 
accumulating a count of the bit errors detected in 
the pattern until the test has ended. If “n” displays, 
retry the test 5 times by ending the test per Step 11 
and re-starting the test per Step 4. If the circuit 
pack never synchronizes, substantial bit errors in 
the 3-in-24 pattern are likely. This could be 
intermittent connections or a broken wire in a 
receive or transmit pair in the CPE wiring.
Bit Error Count Cumulative 
count of 
detected errors
 If there are no wiring problems, the counter 
remains at 0.
A count that pegs at 65535 or continues to 
increment by several hundred to several thousand 
on each list meas command execution indicates 
intermittent or corroded connections, severe 
crosstalk, or impedance imbalances between the 
two conductors of the receive pair or the transmit 
pair. Wiring may need replacement.
Note that “ESF error events” counter and the ESF 
performance counter summaries (“errored 
seconds”, “bursty errored seconds”, and so forth) 
will also increment. These counters are not used 
with the loopback jack tests. However, they will 
increment if errors are occurring. Counters should 
be cleared following the test.