Maintenance Object Repair Procedures 
Page 10-648ETR-PT (Enhanced Tone Receiver Port) 
10
1002 ABORT The system could not allocate time slots for the test 
connection. This situation could occur when the system 
is heavily loaded. If the system is not heavily loaded, 
then test the TDM-BUS via the test tdm command. Refer 
to TDM-BUS for details.
1. Retry the command at 1-minute intervals a maximum 
of 5 times.
2. If the test continues to abort, escalate the problem.
1003 ABORT The system could not allocate a Tone-Clock for the test 
connection. This may be caused by a heavy load on the 
system or by a faulted Tone-Clock.
1. Check to see if there are any alarms against the 
Tone-Clock in the port network where the test 
aborted. If so refer to the recommended procedures 
for TONE-BD or TONE-PT.
2. If a new Tone-Clock has been inserted, allow about 
1 minute for maintenance to run on the newly 
inserted circuit pack.
3. Retry the command at 1-minute intervals a maximum 
of 5 times.
4. If the test continues to abort, escalate the problem.
2000 ABORT Circuit Pack’s response to the test request was not 
received within the allowable time period.
1. Retry the command at 1-minute intervals a maximum 
of 5 times. 
2. If the test continues to abort, escalate the problem.
Table 10-187. TEST #42 Tone Detection Verification Test — Continued
Error 
Code
Test 
Result Description/ Recommendation
Continued on next page