Maintenance Object Repair Procedures 
Page 10-606DTMR-PT [Dual Tone Multifrequency Port (TTR)] 
10
Table 10-169. TEST #43 Tone Detector Audit/Update Test 
Error 
Code
Test 
Result Description/ Recommendation
ABORT The system was not able to allocate all the resources 
needed for this test.
1. Wait one minute and try again.
2000 ABORT Response to the test request was not received within the 
allowable time period.
2100 ABORT Could not allocate the necessary system resources to 
run this test.
1. Retry the command at one-minute intervals for a 
maximum of five times.
2. If the test continues to abort, escalate the problem.
FAIL Hardware audit failed.
1. Run the Short Test Sequence: test port PCSSpp sh 
r 1.
2. If the problem persists, the system is still operating 
properly but system capacity is reduced. In order to 
restore the system performance to normal, replace 
the Tone Detector circuit pack containing the 
defective DTMR port.
PASS The DTMR port has been successfully refreshed with its 
translation.
Continued on next page