User Guide
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si 
555-230-123 
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-543DS1-BD (DS1 Interface Circuit Pack) 
10
interface. The test is highly destructive and can only be initiated by a system 
technician-demanded reset board PCSS command.
All trunks on the DS1 Interface circuit pack must be busied out via the system 
technician busy-out board command before running the Internal Looparound 
Test. When the Internal Looparound Test is initiated, maintenance software 
sends appropriate messages to the DS1 Interface circuit pack to start the test. 
The test uses the Tone Generator and Tone Detector to exercise a bit pattern 
consistency test for all ports. If the transmitted and received bit patterns on a 
trunk are different, the test fails.
When the test is complete, the maintenance software sends a stop loop around 
message to the DS1 Interface circuit pack to put the circuit pack back into the 
normal operation mode. All trunks of the DS1 Interface circuit pack are restored 
to the in-service state after the release board command is entered
Table 10-149. TEST #135 Internal Looparound Test 
Error 
Code
Test 
Result Description/ Recommendation
2012 ABORT Internal system error 
1. Retry the command at 1-minute intervals a maximum of 5 times.
1002 ABORT The system could not allocate time slots for the test. The system may be 
under heavy traffic conditions or it may have time slots out-of-service due to 
TDM-BUS errors. Refer to “TDM-BUS” to diagnose TDM-BUS errors. 
1. If system has no TDM-BUS errors and is not handling heavy traffic, repeat 
test at 1-minute intervals a maximum of 5 times.
1003 ABORT The system could not allocate a tone receiver for the test. The system may be 
oversized for the number of Tone Detectors present or some Tone Detectors 
may be out-of-service.
1. Resolve any “TTR-LEV” errors in the Error Log.
2. Resolve any “TONE-PT” errors in the Error Log.
3. If neither condition exists, retry the test at 1-minute intervals a maximum 
of 5 times.
1004 ABORT Received an incoming call on a port of the DS1 circuit pack during the test.
1. Enter the busy-out board PCSS command to put all trunks of DS1 
Interface circuit pack to out-of-service state.
2. Retry the command at 1-minute intervals a maximum of 5 times.
1015 ABORT Ports on DS1 Interface circuit pack have not been busied out.
1. Enter the busy-out board PCSS command to put all trunks of the DS1 
Interface circuit pack into out-of-service state.
2. Retry the command.
Continued on next page