Maintenance Object Repair Procedures 
Page 10-501DIOD-DS1 (DS1 DIOD Trunk) 
10
b. Error Type 15—This is a software audit error that does not indicate any 
hardware malfunction. Run Short Test Sequence and investigate 
associated errors (if any).
c. Error Type 18—System Technician has busied out the trunk to the 
out-of-service state. No calls can be made on this trunk except the Facility 
Access Test Call. For details on this feature, refer to "Facility Test Calls" 
section in Chapter 5, "Routine Maintenance Procedures".
d. Error Type 130—This error type indicates that the circuit pack has been 
removed or has been insane for more than 11 minutes. To clear the error, 
reinsert or replace the circuit pack.
e. Error Type 257—The DS1 Interface circuit pack detects a hardware fault. 
Aux Data 57392 indicates no external release on PBX disconnect. 
Escalate the problem.
f. Error Type 513—The DS1 Interface circuit pack detects a hardware fault. 
Aux Data 57393 indicates belated external release on PBX disconnect. 
Escalate the problem.
g. Error Type 769—The DS1 Interface circuit pack detects a hardware fault. 
The Aux Data field contains the following error type:
—57484, fault is 
detected on tip/ring. Escalate the error.
h. The DS1Interface circuit pack detects a hardware fault, and the Aux Data 
field contains the following error type: 51200, port is unavailable. Run the 
Dial Tone Test (#314) and follow procedures.
i. Error Type 1793—DS1 Interface circuit pack is out-of-service. Look for 
UDS1-BD errors in the Hardware Error Log if the port is on a TN464 UDS1 
board. Refer to the UDS1-BD (DS1 Trunk Circuit Pack) Maintenance 
documentation for details
j. Error Type 2049—With the following Aux Data:
Aux Data 57473—Rotary dial rate below 8 pulses per second.
Aux Data 57474—Rotary dial rate above 12 pulses per second.
Aux Data 57475—Rotary Dial interdigit time is too short.
The DS1 interface circuit pack detects a hardware error on the DS1 DIOD 
trunk. The trunk can not communicate with the far-end because it is 
unable to interpret digits sent from the far-end switch. Check with the 
far-end switch or Operating Company for proper trunk connection.
k. Error Type 2305—Recorder message, trunk could not be seized (Aux Data 
50944). Run Test #314 and follow the outlined procedures.
l. Error Type 2562—Retry Failure error. This error is logged only. It is not a 
hardware failure and hence does not start any testing or generate any 
alarms. This error comes from call processing and is generated when a 
second attempt (retry) to seize an outgoing trunk fails.