Maintenance Object Repair Procedures 
Page 10-442DID-DS1 (DS1 DID Trunk) 
10
FAIL Test failed due to Internal System Error.
1. Retry the command at one-minute intervals a 
maximum of five times.
2. If test continues to fail, escalate the problem.
PASS Trunk translation has been updated successfully. The 
current trunk states kept in the DS1 Interface circuit 
pack and switch software are consistent. If the trunk is 
busied out, the test does not run, but returns PASS. To 
verify that the trunk is in-service:
1. Enter status-command to verify that the trunk is 
in-service. If the trunk is in-service, no further action 
is necessary. If the trunk is out-of-service, continue 
to Step 2.
2. Enter release-trunk command to put trunk back into 
in-service.
3. Retry the test command.
0NO 
BOARD
The test could not relate the internal ID to the port (no 
board). This could be due to incorrect translations, no 
board is inserted, an incorrect board is inserted, or an 
insane board is inserted.
1. Check to ensure that the board translations are 
correct. Use the list config command, and resolve 
any problems that are found.
2. If the board was found to be correctly inserted in 
step 1, issue the busyout board command.
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should 
re-establish the linkage between the internal ID and 
the port. If this is not the case, check to see that 
there is a valid board inserted.
Table 10-123. TEST #36 Port Audit and Update Test — Continued
Error 
Code
Test 
Result Description/ Recommendation