Maintenance Object Repair Procedures 
Page 10-333CO-TRK (CO Trunk) 
10
Table 10-93. CO Trunk Errors with NO Tests 
Error 
Type
Aux 
Data Description and System Action System Technician Action
1 57347 Port error. Ringing without ground. This 
error is detected on an incoming call on 
a ground-start CO trunk. The CO trunk 
circuit pack has not detected a Tip 
ground before ringing current is 
detected. This may indicate that the 
ground detector is not working. 
However, the call is accepted.
See Note 1 at end of table.
257 50176 Battery reversal detected. This is 
usually caused by the CO (often seen 
with step-by-step and cross-bar offices 
in connection with outgoing calls). This 
is detected if the direction of the loop 
current changes from normal to reverse 
for at least 40 msec. Could occur if the 
trunk was just installed and for some 
reason the Tip and Ring wires were 
reversed at the PBX. If battery reversals 
occur during dialing, wrong numbers 
may result. The CO should be asked to 
remove the battery reversal option.
Refer problem to CO.
513 57364 Ground detector stuck active. After 
several occurrences, an on-board minor 
alarm is generated.
Run short test. If test aborts 
with Error Code 1000, 
disconnect Tip and Ring and 
repeat short test. If test still 
aborts, replace circuit pack. 
If test passes, refer problem 
to CO. If any other error code 
is received, pursue that 
problem.
769 57392 CO not releasing after call is dropped 
from PBX end (off-board alarm after 
several occurrences), or the loop is not 
open after a disconnect (on-board 
alarm after several occurrences).
For off-board alarm, refer 
problem to CO. For on-board 
alarm, the circuit pack has an 
on-board problem (for 
example, stuck relay) and 
should be replaced.
Continued on next page