User Guide
DEFINITY Enterprise Communications Server Release 5
Maintenance and Test for R5vs/si 
555-230-123 
Issue 1
April 1997
Maintenance Object Repair Procedures 
Page 10-279CARR-POW (Carrier Port Power Unit) for AC-Powered Systems 
10
FAIL
(cont’d.)
4. If the replaced power unit still does not operate 
properly, then a circuit pack or a defective 
telephone connected to a circuit pack in the affected 
carrier may be causing an electrical load which is 
preventing the power unit from operating properly. 
Unseat all the circuit packs in the carrier and reissue 
the recycle carrier command.
a. If the recycle passes, then the power units are 
healthy, and the problem is with one of the circuit 
packs. Reinsert the circuit packs one at a time. If 
the status LED shows red after reinserting a 
circuit pack, replace the defective circuit pack. If 
the status LED still shows red, remove the 
Amphenol. connector on the back of the slot 
containing this circuit pack and reissue the 
recycle carrier command. If the status LED 
shows green, the problem is with one of the 
telephones or the wiring to one of the telephones 
on this slot. If the status LED still shows red, 
escalate the problem.
b. If either power unit still shows a red status LED, 
check for bent pins and cable placement in the 
affected carrier. There are failures that can occur 
on the Maintenance/Tape Processor, Duplication 
Interface, and EPN Maintenance circuit pack that 
are not detected by the respective maintenance, 
but that cause many, if not all, environment tests 
to fail. If many environment tests are failing, the 
suspect circuit pack, depending on the system 
configuration, should be replaced and the test 
rerun. If no other problems can be found, 
escalate the problem.
Table 10-83. TEST #127 Power Unit Query Test  — Continued
Error 
Code
Test 
Result Description/ Recommendation
Continued on next page