DEFINITY ECS Release 8.2 Maintenance for R8.2csi 
555-233-119  Issue 1
April 2000
Maintenance Objects 
3-233ATM-TRK (Circuit Emulation Service Circuit Pack) 
3
e. Error Type 257: Control Channel Loop Test #52 failed. The circuit pack is 
not properly connected with the control channel on the TDM bus.
1.  Take the corrective action specified by Test #52?.
f. Error Type 513: ATM Crosstalk Test (#1298) failed. The board is writing to 
or reading from a TDM time slot that is not allocated to the board, or the 
Digital Signal Processor (DSP) selected for this test has malfunctioned. 
1. Run 
test board UUCSS
.
2. Take the corrective action specified for Test #1298. 
g. Error Type 769, 770: the ATM switch is requesting too many LAPD 
retransmissions (off-board ATM cell corruption errors). 
1. Check the connections between the fiber cable, the ATM-TRK 
circuit pack, and the ATM switch.
2. See the PKT-BUS for test and corrective procedures (Aux Data 35 
only).
3. Determine what type of fiber is installed between the ATM-TRK 
circuit pack and the ATM switch.
Error
Type
Aux 
Data Description
769 35 LAPD excessive retransmission requests
770 25 ATM uncorrectable cell headers - threshold
If Then
There is multimode fiber  Check the length of the fiber. If the cable 
is longer than 2 km, it is probably causing 
the errors. 
There is single-mode fiber 
or the length of the 
multimode fiber is less 
than 2 km
The source of the errors may lie in the 
ATM facility, the ATM-TRK circuit pack, or 
the far-end circuit pack. 