User manual
DEFINITY ECS Release 8.2 Maintenance for R8.2csi 
555-233-119  Issue 1
April 2000
Maintenance Objects 
3-212V-PWR (12 Volt Power Supply) 
3
Error Log Entries and Test to Clear Values
System Technician-Demanded Tests: Descriptions 
and Error Codes
Always investigate tests in the order presented in the following table. By clearing 
error codes associated with the 
12 Volt Power Supply Test
 for example, you may 
also clear errors generated from other tests in the testing sequence. The 12 Volt 
Power Supply Test can be initiated through either the 
test card-mem
 command 
or the 
test network-control
 command.
Table 3-1. 12 Volt Power Supply Error Log Entries
Error 
Type
Aux 
Data Associated Test Alarm Level
On/Off 
Board
Test to  Cle ar  
Val ue
0
1
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the 
appropriate test description and follow the recommended procedures.
0 Any Any Any test card-mem
1
2
2. Software cannot turn on the 12 volt power supply to provide 12 volt power to the flash memory or to 
the translation card.
Any 12 Volt Power Supply Test 
(#701)
MINOR ON test card-mem
257
3
3. Software can turn on the 12 volt power supply, and 12 volt power is available. However, the software 
cannot turn the power supply off after operations are completed. The 12 volt power remains on. This 
error does not affect the normal operations involved in accessing the memory or the translation 
card.
Any 12 Volt Power Supply Test 
(#701)
WARNING ON test card-mem
Table 3-2. System Technician-Demanded Tests: 12-V PWR
Order of Investigation
Short Test 
Sequence
Long Test 
Sequence
Reset Board 
Sequence D/ND
1
12 Volt Power Supply Test (#701) X X ND
Memory Card Insertion Test (#695)
2
XX ND
Memory Card Format and Read Test (#696)
2
XX ND
Memory Card Match Test (#697)
2
XX ND
Memory Card Write-Protected Test (#698)
2
XX ND
Continued on next page