User manual
DEFINITY ECS Release 8.2 Maintenance for R8.2csi 
555-233-119  Issue 1
April 2000
 Maintenance Objects
3-1081TDM-CLK (TDM Bus Clock) 
3
Notes:
a. The Tone-Clock circuit pack may have a clock at the edge of its specified 
frequency. This can is turn cause Remote Neighbor Links (RNLs) and/or 
Local Neighbor Links LNLs) to go down. When this error is alarmed, Clock 
Health Inquiry Test (#46) will fail with an error code of 1.
1. Replace the Tone-Clock circuit pack identified in the error log.
b. The indicated Tone-Clock circuit pack has been made unavailable via the 
busyout tone-clock PC
 command. To resolve this error, execute the 
release tone-clock PC
 command for the alarmed circuit pack.
c. This error type indicates that the circuit pack has been removed or has 
been insane for more than 11 minutes. To clear the error, reinsert or 
replace the circuit pack.
d. The Tone-Clock circuit pack in the PPN is not a TN780 while a Stratum 3 
synchronization is administered. Replace the Tone-Clock in the PPN with a 
TN780, or change synchronization administration to Stratum 4 if a Stratum 
3 clock is not being used.
e. The tone-clock has reported an out-of-lock condition. A aux value of 1 
indicates this error is an out-of-lock with the primary reference. A aux 
value of 2 indicates this error is an out-of-lock with the secondary 
reference. It could not lock onto the frequency of that synchronization 
reference. This will lead to a change in the synchronization reference if the 
condition continues.
2049(i) Any Standby Reference 
Health Check 
Test(#651)
MAJOR
3
ON test tone-clock PC
2305(j) 0 None WARNING OFF
1. As a general rule, any 
on board
 errors against the TDM Bus Clock should be resolved before 
pursuing any other errors against SPE or PNC components. 
Off board
 clock errors may be caused 
by other board errors, and should usually be addressed once any on board errors have been 
resolved.
2. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
3. Major or Minor alarms on this MO may have been downgraded to Warning alarms based on the
values used in the set options command.
Table 3-480. TDM Bus Clock Error Log Entries — Continued
Error 
Type
Aux 
Data Associated Test
Alarm 
Level
On/Off 
Board
1
Test to Clear Value
Continued on next page