 Maintenance Objects
3-966PRI-CDR/SEC-CDR (PRI-CDR Link) 
3
Link Retry Test (#215)
This test sends a message to the CDR software process to make a data call to 
the extension where the CDR output device connects to or opens the EIA port to 
the CDR output device. If the CDR link is already up, this test is passed without 
making any data call or opening the EIA port.
Table 3-421. TEST #213 Link Tear Down Test 
Error 
Code
Te s t 
Result Description/ Recommendation
40 ABORT Internal system error
50 ABORT Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
1010 ABORT The CDR link has been busied out to out-of-service.
1. Enter the release cdr-link primary|secondary command to release the 
CDR link from busyout state.
2. Retry the test cdr-link primary|secondary long command to execute the 
test.
FAIL Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
PASS The CDR link is torn down.
Continued on next page